RIDE model ice machine ventilation and exhaust requirements
Fabricator-supplied, custom air intake grilles must have 12" x 12" (30.5 cm x 30.5 cm) opening yielding
100 sq. inches (645 sq. cm) of open air space within duct perimeter. Block off any open area outside of the air duct.
Intake air requirements — air-cooled ice machines (MCD400AHS, MCD400AVS & R400A only)
1. Check that 2" (51 mm) duct is installed on condenser front.
2. Cut a 12" x 12" (30.5 cm x 30.5 cm) opening in counter face to align with duct.
3. Position ice machine to mate duct flush with back of counter opening.
4. Install supplied grille on outside of counter opening.
Exhaust air — all ice machines (MCD400A/W & R400A/W)
Provide 100 sq. in. (645 sq. cm) of counter opening for exhaust air at least 18" (45.7 cm) from intake opening but not
more than 10 ft (3 m) away.
MCD400AHS, MCD400AVS & R400A — Side View
Standard
louvered grille
(supplied)
Air intake
Supplied 2" (51mm) duct MUST be installed
to front of ice machine and mated flush to inside
of counter face opening.
Front View
Standard 2" (51 mm)
duct mates counter
opening (behind
grille) to condenser
front
Air in
through louver
14
T400A/W, MCD400A/W, R400A/W, MFD400A/W, D400A/W Ice Machines
Exhaust air
Exhaust air
out side to
opening at least
18" (45.7) cm
from air intake
Air out through louver
Provide at least 100 sq. in.
(645 sq. cm) of counter
opening for exhaust air