Krom Schroder JSAV 25 Operating Instructions Manual

Safety shut-off valve

Advertisement

Quick Links

0500 · Edition 0.
D
GB
F
NL
I
TR
CZ
PL
RUS
H
 
Operating instructions
Safety shut-off valve JSAV 5 – 40
Translation from the German
© 2012 Elster GmbH
Contents
Contents
Safety shut-off valve JSAV 5 – 40 . . . . . . . . . 
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
Checking The Usage . . . . . . . . . . . . . . . . . . . . . 
Type Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Part Designations . . . . . . . . . . . . . . . . . . . . . . . . 2
Type Label. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
Connecting The Impulse Line . . . . . . . . . . . . . . 
Tightness Test . . . . . . . . . . . . . . . . . . . . . . . . . . 
Checking The Function . . . . . . . . . . . . . . . . . . . 4
Checking The Trip Pressure . . . . . . . . . . . . . . . . . 4
Setting The Trip Pressure . . . . . . . . . . . . . . . . . 4
Replacing The Spring . . . . . . . . . . . . . . . . . . . . 4
Resetting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Replacing The Measuring Unit. . . . . . . . . . . . . 5
Replacing The Valve Disc . . . . . . . . . . . . . . . . . 6
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . 7
Designed Lifetime . . . . . . . . . . . . . . . . . . . . . . . . 8
Declaration Of Conformity . . . . . . . . . . . . . . . . 8
Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
E
DK
S
N
P
GR
www.docuthek.com
Safety
Safety
Please read and keep in a safe place
Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the opera-
tor. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
• ,  ,  ,  ... = Action
= Instruction
Liability
We will not be held liable for damages resulting
from non-observance of the instructions and non-
compliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Transport
On receipt of the product, check that the delivery is
complete (see Part designations). Report any trans-
port damage immediately.
Storage
Store the product in a dry place. Ambient tempera-
ture: see Technical data.
GB-1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the JSAV 25 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Krom Schroder JSAV 25

  • Page 1 Safety Safety 0500 · Edition 0. Please read and keep in a safe place www.docuthek.com   Please read through these instructions Operating instructions carefully before installing or operating. Following the Safety shut-off valve JSAV 5 – 40 installation, pass the instructions on to the opera- tor.
  • Page 2: Part Designations

    Type label Checking the usage ▷ Max. inlet pressure p , upper trip pressure p JSAV and lower trip pressure p , ambient tempera- Safety shut-off valve for securing downstream fittings ture T: see type label. against excess gas pressure. www.kromschroeder.com This function is only guaranteed when used within D-49018 Osnabrück, Germany JSAV the specified limits –...
  • Page 3 ▷ We recommend installing a manual valve AKT 25 Tightness test in the pipe leading to the safety relief valve VSBV 25, so that the annual function check of WARNING the safety shut-off valve JSAV can be carried out – An additional tightness test must be carried without having to remove it.
  • Page 4: Checking The Trip Pressure

    Checking the function Setting the trip pressure  Select the upper trip pressure p according to Checking the trip pressure the outlet pressure p of the pressure regulator. The JSAV is checked for the required trip pressure.  Vent the system. ▷ Ensure that the valve seat of the JSAV is open, see page 5 (Resetting).
  • Page 5: Resetting

    ▷ Attention! The individual parts are compressed. Resetting Part designations ▷ Ensure that the pressure of the impulse line is between the upper and lower trip pressure.  Remove the breather screw plug.  Turn the reset cap and pull it approx. 1 to 2 mm (0.04 to 0.08") upwards.
  • Page 6: Replacing The Valve Disc

    6 Follow the reverse procedure when reassembling. Replacing the valve disc 7 Connect the impulse line to the JSAV. ▷ The valve disc has to be replaced if the JSAV 8 Check tightness and function, see page  3 is leaking. (Tightness test) and page ...
  • Page 7: Maintenance

    Maintenance In order to ensure smooth operation: Check the function and tightness of the JSAV every year, or every six months if operated with biologically produced methane, see page  4 (Checking the function) and page 3 (Tightness test). ▷ In the case of malfunctioning, check the measuring unit and valve disc and replace if necessary.
  • Page 8: Designed Lifetime

    We, the manufacturer, hereby declare that the prod- use in the long term, a clean method of operation ucts JSAV 25 – 40, marked with product ID No. CE- and safe function. 0085AS0202, comply with the requirements of the The service life on which the construction is based, listed Directives and Standards.

This manual is also suitable for:

Jsav 40

Table of Contents