Connect the power cables

See figures
C
(page 19) D, E, F1,
1. Remove the rubber grommets from the lead-through plate.
R0-
Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE
R3
conductor for drive or motor, make sure that is has sufficient conductivity for the PE.
R6-
2. Cut an adequate hole into the rubber grommet. Slide the grommet onto the cable.
R9
3. Prepare the ends of the motor cable as illustrated in figures 3a and 3b. Two
different motor cable types are shown. Note: The bare shield will be grounded
360 degrees. Mark the pigtail made from the shield as a PE conductor with
yellow-and-green color.
4. Slide the cable through the hole of the bottom plate and attach the grommet to the
EN
hole.
5. Connect the motor cable:
DA
Ground the shield 360 degrees by tightening the clamp of the power cable
DE
grounding shelf onto the stripped part of the cable (5a).
Connect the twisted shield of the cable to the grounding terminal (5b).
ES
Connect the phase conductors of the cable to the T1/U, T2/V and T3/W
terminals (5c). Tighten the screws to the torque given in the figure.
FI
6. Repeat steps
FR
7. Connect the input power cable. Connect the additional PE conductor of the cable
(7c). Tighten the screws to the torque given in the figure.
IT
8. Install the grounding shelf for the brake resistor cable.
NL
9. Repeat steps
conductors (if any).
PL
10. Connect the resistor cable (if used). Tighten the screws to the torque given in the
figure.
PT
11. Install the grounding shelf for the control cables.
RU
12. Put the unused rubber grommets to the holes in the lead-through plate.
SV
13. Secure the cables outside the unit mechanically.
14. Ground the motor cable shield at the motor end. For minimum radio frequency
TR
interference, ground the motor cable shield 360 degrees at the lead-through of
the motor terminal box.
ZH
F2
2...4
for the input power cable.
2...4
for the brake resistor cable (if used). Cut off extra phase
and G.