32 EN – R6...R9 Quick installation guide

Select the power cables

Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.

Ensure the cooling

R0-
R3
See table
I
on page
R6-
maximum ambient temperature is 40 C (+104 °F). No condensation or frost is
R9
allowed. For more information on the ambient temperature, see chapter Technical
data in ACH580-01 hardware manual (3AUA0000076331 [English]).

Protect the drive and input power cable

See tables III,
IV
EN
If you use gG fuses, make sure that the operating time of the fuse is below
0.5 seconds. Follow the local regulations.
DA

Install the drive on the wall

DE
ES
Warning! The drive module is heavy (45 to 98 kg / 99 to 216 lb). Use a suitable
lifting device. Do not lift the module manually. Make sure that the wall and the
FI
fixing devices can carry the weight.
FR
See figure
R6...R9 Figures A
IT
NL
PL
PT
RU
SV
TR
ZH
27
(UL: table
II
on page 27) for the heat dissipation. The
and
V
on pages
28
and
on page 41.
29
for the fuses.