Installation Of Outdoor Unit - Gree GMV-36WL/A-T(U) Manual

Dc inverter side discharge vrf ii
Hide thumbs Also See for GMV-36WL/A-T(U):
Table of Contents

Advertisement

DC Inverter Side Discharge VRF Ⅱ for North America
2.4 Communication cable and control cable
Note: For air conditioning units installed in places with strong electromagnetic
interference, shielded wire must be used as the communication cables of the IDU and
wired controller, and shielded twisted pairs must be used as the communication cables
between IDUs and between the IDU and ODU.
Communication cable selection for ODU and IDUs
Communication Cable
Material Type
between IDU Unit and
IDU (ODU ) Unit L(m/feet)
Light/Ordinary
polyvinyl chloride
sheathed cord.
2.5 Power cable
Only copper conductors can be used as power cables. The copper conductors must
meet relevant national standard and satisfy the carrying capacity of unit.
2.6 Hanger rod and support
Hanger rod: M8 or M10;
(1)
U-steel: 14# or above;
(2)
Angle steel: 30mm×30mm×3mm or above;
(3)
Round steel: Φ10mm or above
(4)

3 Installation of outdoor unit

3.1 Check before installation
Before installation, please check the power cord if it complies with the power supply
(1)
requirement on the nameplate. Make sure the power supply is safe.
This air conditioner must be properly grounded through the receptacle to avoid
(2)
electric shock. The ground wire shouldn't be connected with gas pipe, water pipe,
lightning arrester or telephone line.
Maintain good air circulation to avoid lacking oxygen.
(3)
Read this manual carefully before installation.
(4)
3.2 Selection of installation site
Select a location which is strong enough to hold unit's weight so that unit can stand
(1)
still and erect.
Total Length of
L≤1000(3280-5/6)
Wire size
1) If the wire diameter is enlarged
to 2×AWG16, the total
communication line length can
reach 1500 m (4921-1/4feet).
2) The cord shall be Circular cord
≥2×AWG18
(the cores shall be twisted
together).
3) If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to
use shielded wire.
68
Remarks

Advertisement