INSTALLATION MANUAL
GENERAL
Model BUZ units are factory assembled heat pumps designed for
outdoor installation on a roof top or a slab. Field-installed electric
heater accessories are available to provide supplemental electric
heat combined with electric cooling and heating.
The units are completely assembled on rigid, removable base
rails. All piping, refrigerant charge, and electrical wiring is fac-
tory installed and tested. The units require only electric power
and duct connections at the point of installation.
The electric heaters have nickel-chrome resistance wire ele-
ments and utilize single point power connection.
INSPECTION
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier's freight bill.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the
installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury
and/or equipment damage may result if installation procedure is not handled properly.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS
AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELEC-
TRICAL, AND MECHANICAL CODES
INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE
PERSONAL INJURY, PROPERTY DAMAGE AND/OR DEATH.
DE-ENERGIZE THE ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING TO INSPECT, REPAIR OR PERFORM
MAINTENANCE TO THE UNIT.
THIS SYSTEM USES R-410A REFRIGERANT WHICH OPERATES AT HIGHER PRESSURES THAN R-22. NO OTHER RE-
FRIGERANT MAY BE USED IN THIS SYSTEM.
SINGLE PACKAGE HEAT PUMPS
Supersedes: Nothing
MODELS BAUZ024 THRU 060
2 THRU 5 TON
WITH R-410A REFRIGERANT
(13 SEER)
A separate request for inspection by the carrier's agent should
be made in writing. Refer to Form 50.15-NM for additional infor-
mation.
REFERENCE
Additional information on the design, installation, operation
and service of this equipment is available in the following refer-
ence forms:
• 55.70-N1
• 55.70-N2
• 035-16605-003 — Electric Heater Accessory
REPLACEMENT PARTS
• Refer to User's Maintenance and Service Information
Manual for complete listing of replacement parts on this
equipment.
CAUTION
WARNING
WARNING
CAUTION
035-20188-000-A-0704
— General Installation
— Pre-start & Post-start Check List

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BAUZ Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group BAUZ Series

  • Page 1 INSTALLATION MANUAL SINGLE PACKAGE HEAT PUMPS 035-20188-000-A-0704 Supersedes: Nothing MODELS BAUZ024 THRU 060 2 THRU 5 TON WITH R-410A REFRIGERANT (13 SEER) GENERAL A separate request for inspection by the carrier's agent should be made in writing. Refer to Form 50.15-NM for additional infor- Model BUZ units are factory assembled heat pumps designed for mation.
  • Page 2: Installation

    Unit must be installed on a level roof curb or appropriate an- gle iron frame providing adequate support under the com- FIG. 1 - CENTER OF GRAVITY pressor/condenser section. Unitary Products Group...
  • Page 3 A condensate trap is required to be installed in the condensate drain. The plumbing must conform to local codes. Use a seal- ing compound on male pipe threads. Install the condensate drain line ( " NPTF) to spill into an open drain. " Unitary Products Group...
  • Page 4: Power Wiring

    POWER WIRING REFER TO ELECTRICAL DATA REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCON- TABLES TO SIZE THE DISCON- NECT SWITCH, WIRING & NECT SWITCH, WIRING & OVERCURRENT PROTECTION. FIG. 2 - TYPICAL FIELD WIRING DIAGRAM Unitary Products Group...
  • Page 5 208/230-3-60 17.6 120.0 0.96 460-3-60 70.0 39.4 0.96 1 = Rated in accordance with ARI Standard 110, utilization range “A”. 2 = Dual element, time delay type. NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER ELECTRIC HEAT CORRECTION FACTORS Unitary Products Group...
  • Page 6 = KW listed is for 240 volts, use table on previous page for 208 or 230 volts. = Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused. = KW listed is for 480 volts, use table on previous page for 460 volts. Unitary Products Group...
  • Page 7 NOTE: FOR UNITS APPLIED WITH A ROOF CURB, THE MINIMUM CLEARANCE MAY BE REDUCED FROM 1 INCH TO 1/2 INCH BE- TWEEN COMBUSTIBLE ROOF CURB MA- TERIAL AND THE SUPPLY DUCT. FLEXIBLE DUCT COLLAR FIG. 2 - CLEARANCES Unitary Products Group...
  • Page 8 "! " " & & OUTDOOR " BACK COIL & CONDENSATE DRAIN “ NPTI SIDE RETURN " AIR OPENING BOTTOM SUPPLY AIR OPENING " & " " & BOTTOM RETURN AIR OPENING " FIG. 4 - DIMENSIONS Unitary Products Group...
  • Page 9: Cooling Operation

    Only a power cycle will clear this state. the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust tem- perature settings within the limitations of the system. Unitary Products Group...
  • Page 10 HEATER BANK 3 ELEC. HEAT 20 SEC. DELAY ON “W” HEATER BANK 3 ELEC. HEAT INSTANT OFF HEATER BANK 2 ELEC. HEAT SEC. DELAY OFF HEATER BANK 1 ELEC. HEAT 1 SEC. DELAY OFF FAN 10 SEC. DELAY OFF Unitary Products Group...
  • Page 11 HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON “W” HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF HEATER BANK 1, 2 & 3 ELEC. HEAT SEC. DELAY OFF FAN 10 SEC. DELAY OFF Unitary Products Group...
  • Page 12: Normal Maintenance

    CAUTION: If the variable speed motor found in the BAUZ connections with line terminals. models operates erratically, check the fan control board for the presence of a break-off tab. Remove tab if present. Unitary Products Group...
  • Page 13 035-20188-000-A-0704 FIG. 5 - TYPICAL WIRING DIAGRAM BUZ MODELS- 208/230-1-60 POWER SUPPLY Unitary Products Group...
  • Page 14 035-20188-000-A-0704 FIG. 6 - TYPICAL WIRING DIAGRAM BUZ - 208/230-3-60 POWER SUPPLY Unitary Products Group...
  • Page 15 035-20188-000-A-0704 FIG. 7 - TYPICAL WIRING DIAGRAM BUZ - 460-3-60 POWER SUPPLY Unitary Products Group...
  • Page 16 If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all filter driers. FIG. 8 - R-410A QUICK REFERENCE GUIDE Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A.

This manual is also suitable for:

Bauz024Bauz030Bauz036Bauz042Bauz048Bauz060

Table of Contents