Connecting The Condensate Drain; Condensate Drain; Connecting The Neutralising System (Accessories); Flue Gas Connection - Viessmann VITOCROSSAL Series Installation Instructions Manual

Gas condensing boiler with matrix cylinder burner
Table of Contents

Advertisement

Connecting the condensate drain

Condensate drain

Connect the trap with the plastic hose to the drain-
age system.
Route the condensate drain with a fall and below the
anti-flooding level of the flue gas collector.

Connecting the neutralising system (accessories)

Installation instructions "Neutralising system"
Fig. 47
Drain hose from trap to neutralising system,
A
external
of connection: 17 mm
7
Drain hose from neutralising system to drainage
B
system
Neutralising system
C

Flue gas connection

Connections on the flue gas side

Note
Ensure the flue gas connection is free of load and tor-
que stress.
Flue system installation instructions
Flue gas connection:
Do not carry out commissioning until the following
conditions are met:
Free passage through the flue gas pipes.
Flue system with positive pressure is gas-tight.
Inspection port covers checked for secure and tight
seating.
A
B
C
200 mm
7
The condensate drain must be freely accessible for
inspection where it enters the drainage system.
Condensate drain hose connection, outer
1. Position neutralising system
2. Connect drain hose
3. Connect neutralising system drain hose
drainage system.
!
Please note
Balanced or standard flues must not come
loose.
Use floor or wall mounted fixing clamps (bal-
anced flue system accessories) to secure the
pipes in place.
Connect the flue outlet to the flue with the shortest
possible run, maintaining a slight rise (min. 3°). Avoid
sharp kinks.
Apertures for ensuring sufficient combustion air sup-
ply are open and cannot be closed off.
Applicable regulations on installing and commission-
ing flue systems have been followed.
: 17 mm
7
C
behind the boiler.
to the trap.
A
to the
B
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents