COOPER POWER Surge Arresters SERIES Effective January 2017 MN235012EN Supersedes July 2011 (IS235-82-1) VariSTAR Type AZG2 Surge Arresters Installation and Maintenance Instructions VariSTAR SURGE ARRESTER ® AZG2 Cat. No. Olean, N.Y. Ser. No. Year Rating kV rms MCOV/COV kV rms Pres.
Page 2
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to...
FOR LIFE FOR LIFE Eaton’s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing and service.
Handling and storage CAUTION: If the arrester is to be stored for an appreciable time before Eaton’s Cooper Power series VariSTAR Type AZG2 surge installation, provide a clean, dry storage area. Locate the arrester is designed to be operated in accordance with arrester so as to minimize the possibility of physical damage.
CAUTION: 0.866 C The values shown in Table 1 are the minimum clearances recommended by Eaton . These minimum clearances may be increased to meet local or system requirements for spacing of energized equipment . Safe operating practices DIRECTED must always be followed .
VariSTAR Type AZG2 Surge Arresters Installation and Maintenance Instructions 1.11 cm DIA HOLES ON 7.62 cm 4.44 cm CENTERS TYPICAL 4 PLACES STAINLESS GALVANIZED STEEL STEEL BOLTS CLAMP 1.90 cm ALUMINUM ALLOY 4.44 cm 9.52 cm “A” “A” “A” 1.43 cm DIA HOLES ON 4.44 cm CENTERS VIEW 1...
Page 8
VariSTAR Type AZG2 Surge Arresters Installation and Maintenance Instructions PLACE UNDER LINE TERMINAL = 132-240 kV Digits 6 & 7 of Part No. Arrester Catalog No. AT76Y1 18-21 AT76Y2 22-25 Figure 8 . Grading ring assembly . Arresters with extra creepage housing may require ote: grading rings in different voltage ratings.
Page 9
VariSTAR Type AZG2 Surge Arresters Installation and Maintenance Instructions Table 1 . Catalog Numbers and Dimensional Information for Standard Arresters (Contact Eaton Representative for Catalog Numbers of Non-standard Arresters) Dimension Housing Ur Arrester Dimension B C Minimum Creepage Rating Uc COV .
Page 10
VariSTAR Type AZG2 Surge Arresters Installation and Maintenance Instructions This page is intentionally left blank. INSTALLATION AND MAINTENANCE INSTRUCTIONS MN235012EN January 2017...
Page 11
VariSTAR Type AZG2 Surge Arresters Installation and Maintenance Instructions This page is intentionally left blank. INSTALLATION AND MAINTENANCE INSTRUCTIONS MN235012EN January 2017...