Channels
Technical Data
Operational supply:
Power consumption:
Product rating & recommended circuit protection: 16A or 20A MCB
Maximum switched live load (per channel):
Max total switched live load:
Digital dimming ballasts per channel:
Digital dimming ballasts per LCM:
1-10V dimming ballasts per channel:
Maintained live output:
VF output:
SELV output:
Mains supply terminal capacity:
Mains switched live output connection:
Override switch input connector:
MLS bus connector:
MLS bus cable:
Case material:
Case finish:
IP rating:
Dimensions
Width (W) = 213 mm
Height(H) = 62 mm
Depth(D) = 91 mm
Weight
= 0.62kg approx
Enclosure
An enclosure (K5612S MET) is available for this product.
It provides integral connection bars fitted with link and features a robust galvanized metal base, lid and door.
The DIN rail embodies a useful alignment and fixing mechanism that allows quick installation.
Cable entry points are located on top, bottom, side and rear surfaces.
Colour:
Dimensions:
Protection:
Switched
Mains
Dimming
Live Outputs
Input
Channels
230VAC ~50Hz/60Hz
18W maximum
6 A
16A
10 maximum
40 maximum
20mA (sinking only). See manufacturer's specification: worst case 10 Ballasts but Philips HF-R, for example,
20 Ballasts. Observe switched live load limit above.
6A
6A
1A @ 24V AC/DC
2x2.5mm² or 1x4mm²
1x2.5mm² or 1x4mm²
2.5mm²
2.5mm²
Two-core multi-stranded twisted pair Cross-sectional area 1.5mm² unscreened 600/1000V rated
LSOH insulated: see Application Note AN4001
Self-extinguishing blend PC/ABS
Gray RAL 7035
20
White
310mm x 244mm x 116mm
BS EN 60529 to IP 2XC