Honeywell Ex-Or CDH8U5 Installation And Commissioning Instructions page 4

8-channel programmable intelligent lighting control module

Advertisement

Easy integration of lighting and AV systems
The AVINTCDR provides an interface between MLS Connect Digital
Intelligent Lighting Control Module (i.e. CDW12U5-B, CDH4U5-B or
CDH8U5-B) or from any Audio Visual system that uses Dynet commands
via RS232 or RS485.
When the Ex-Or interface receives a command from the AV system, the
decoded signal is then sent to the CD Box where it is translated (a
command can recall scenes 1 to 6 of a zone in the range 1 to 100) and can
be forwarded on to the MLS Digital Network if connected to it.
The AVINTCDR allows the AV system to adjust lighting and recall lighting
scenes and behaviors via the Ex-Or MLS Digital Network System. In this
way, initiating a projector presentation, for example, would automatically
adjust the lighting to a suitable scene without needing any separate action
to dim the lights.
The MLS Connect Digital Lighting Control Module provides a gateway to
the wider MLS system but connecting directly to a CDW12U5, CDH4U5 or
CDH8U5 LCM also allows use in non-MLS applications.
Easy touch screen control of AV and lighting
User interface panels or touch screens from the Ex-Or Scene Select II
range can also be used.
Connecting to the MLS Digital Network
It is imperative that the MLS Bus be wired in the correct type of cable.
Normally
it should be Two-core multi-stranded twisted pair Cross-sectional area
1.5mm2 unscreened 600/1000V rated LSOH insulated. Please see
AN4001 from our website to learn further details on the MLS Digital
Network regarding cable needs as it differs according to different designs.
This can make your installation easier.
A MLS Digital Network will need a specific power supply. We offer this MLS
Digital Network power supply integrated in the Model CDH8U5-RB and its
variants CDH8U5-RBA and CDH8U5-RBDALI. Alternatively you can use
the
Rb2000, RB2000LT plus variants on the CDH4U5.
Do not connect Mains to the MLS Bus.
In
In
Out
Out
MLS Bus 1
MLS Bus 2
For connection of Bus Power Supply variants, see also Application Note
AN4030 from our website.
-4-