Analog channel configuration

MPTTR has one analog group input which must be properly configured.
Table 440:
Analog signals
Input
I3P
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of MPTTR can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
The function uses ambient temperature which can be measured locally or remotely.
Local measurement is done by the protection relay. Remote measurement uses analog
GOOSE to connect AMB_TEMP input.
If the quality of remotely measured temperature is invalid or
communication channel fails the function uses ambient temperature
set in Env temperature Set.
I_A
I_B
I3P
I_C
I
AMB_TEMP
START_EMERG
BLOCK
GUID-E9FDBA65-8D30-4430-A156-029C61F4A42A V1 EN
Figure 213:
Functional module diagram
Description
Three-phase currents
Max
current
selector
Thermal
2
level
calculator
Internal
FLC
calculator
1MRS759142 C
ALARM
Alarm and
BLK_RESTART
tripping
logic
OPERATE
TEMP_RL
Technical Manual
REX640