Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.1.2.10
Table 377:
DPHLPDOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Time multiplier
Operate delay time
Table continues on next page
REX640
Technical Manual
Table 374:
DPHHPDOC Input signals
Name
I3P
U3P
BLOCK
ENA_MULT
NON_DIR
Table 375:
DPHLPDOC Output signals
Name
OPERATE
START
FAULT_DIR
DIRECTION
Table 376:
DPHHPDOC Output signals
Name
OPERATE
START
FAULT_DIR
DIRECTION

Settings

Unit
0.05...5.00
xIn
0.8...10.0
0.025...15.000
40...300000
ms
Type
Default
Description
SIGNAL
-
Three-phase currents
SIGNAL
-
Three-phase voltages
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
Enable signal for current multiplier
BOOLEAN
0=False
Forces protection to non-directional
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Enum
Detected fault direction
Enum
Direction information
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Enum
Detected fault direction
Enum
Direction information
Step
Default
0.01
0.05
0.1
1.0
0.005
1.000
10
40
Section 4
Protection functions
Description
Start value
Multiplier for scaling the start value
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
343

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents