Section 3
Basic functions
3.20.17.6
258
If the numbers of channels connected to I3P1...I3P4 and
IRES1...IRES4 does not match with the number of connected
SWITCH_TOx inputs, the configuration of the function fails.
Outputs ALARM and IRES_ALARM indicate bad quality data of system measurements
for selected I3P and IRES, respectively.
Outputs WARNING and IRES_WARNING indicate questionable quality data of
system measurements for selected I3P and IRES, respectively.
Depending on the connected I3P channels to the current switch, the
Primary current settings between the source I3P must match.
Depending on the connected IRES channels, the Primary current
settings between the source IRES must match.
Setting validation for the primary current fails unless they are all
stored simultaneously to the protection relay.

Signals

Table 243:
CMSWI Input signals
Name
Type
I3P1
SIGNAL
I3P2
SIGNAL
I3P3
SIGNAL
I3P4
SIGNAL
IRES1
SIGNAL
IRES2
SIGNAL
IRES3
SIGNAL
IRES4
SIGNAL
SWITCH_TO2
BOOLEAN
SWITCH_TO3
BOOLEAN
SWITCH_TO4
BOOLEAN
Table 244:
CMSWI Output signals
Name
Type
SOURCE1
BOOLEAN
SOURCE2
BOOLEAN
SOURCE3
BOOLEAN
SOURCE4
BOOLEAN
I3P
SIGNAL
Table continues on next page
Default
Description
-
Three-phase currents 1
-
Three-phase currents 2
-
Three-phase currents 3
-
Three-phase currents 4
-
Residual current 1
-
Residual current 2
-
Residual current 3
-
Residual current 4
0=False
Switch to source 2
0=False
Switch to source 3
0=False
Switch to source 4
Description
Selected current source is source 1
Selected current source is source 2
Selected current source is source 3
Selected current source is source 4
Three-phase currents
1MRS759142 C
REX640
Technical Manual