Fit the support bracket around the terminal and secure using appropriate fixings. Do not tighten the
support bracket
8.
Install the remainder of the flue system working progressively away from the water heater supporting the
pipes as necessary.
9.
Once the flue system is fully installed, tighten the clamp to secure the terminal in place.
FIGURE 8.7
VERTICAL TERMINAL ROOF FLASHINGS FOR SYNTHETIC, FLAT AND TILED ROOFS
FIGURE 8.8
8.8.4

TYPE C

43
This appliance can operate on a U-Duct common flue system. The maximum lengths for the interconnecting flue
can be found in Table 3.1.
Concrete components of the U-Duct must meet the requirements of BS EN 1858
Mass Rate @ 100%
Model No.
(@ 9% CO2) (G20)
SHW45-325CE
SHW60-325CE
SHW85-435CE
SHW115-435CE
SHW145-435CE
INSTALLING TERMINAL THROUGH ROOF FLASHING
Mass Rate @ 23%
(@ 9% CO2) (G20)
16.0
3.7
22.3
5.1
30.4
7.0
42.5
9.8
53.2
12.2
TABLE 8.4
FLUE GAS MASS RATES
Mass Rate @ 100%
Mass Rate @ 23%
(@ 10.5% CO2) (G31)
(@ 10.5% CO2) (G31)
16.7
23.2
31.6
44.2
55.4
3.8
5.3
7.3
10.2
12.7
19