NAPCO Gemini GEM-P816 Installation Instructions Manual page 8

Control panel/communicator
Table of Contents

Advertisement

Page 8
Smoke Detectors, 4-Wire:
1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Gentex 812, 812T, 812P, 812PT, 812PH; 8120, 8120T, 8120P, 8120PT, 8120PH
3. Hochiki America SLG-12 with YBC-RL4-RA Base
4. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations, waterflow and
thermostats may be used if acceptable to the Authority having Jurisdiction.
UL Compatible Smoke Detectors (Providing UL Recognition or Listing)
Manufac-
turer
Sentrol
System
Sensor
Note: * Voltage Rating: 8.5–13.3 VDC, Maximum Number of Detectors: 10
Residential
Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.
Initiating loops supervised if longer than 3 feet.
FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors).
Minimum alarm timeout of 5 minutes.
Maximum exit time: 60 seconds.
Maximum entry time: 45 seconds.
Do not program "Swinger Shutdown", "Force Arming", "Selective Bypass", "Bypass", or "50 ms Loop Response".
"Abort Delay" may not exceed 45 seconds.
Program "Disable Callback Download".
Automatic dialer may not dial a police station number that has not been dedicated for such service.
System must be tested at least weekly under AC/battery and Battery-Only conditions.
Replace the rechargeable battery at least every 5 years.
If the battery is heavily discharged, replace it or have it tested by a qualified technician.
For silent panic, connect only to UL-listed holdup devices.
All zones must be programmed for "Priority".
Do not program any zones for "Keyswitch Arming".
System must be serviced at least once every 3 years.
Residential Fire and Combination Residential Fire & Burglary must program "Residential Fire"
Keypad Expansion (EZM) Zones are not to be used as fire zones
"Keypad Auxiliary" is not to be programmed for medical purposes.
"System Trouble Audible Automatic Time-out" is not to be programmed.
"Disable System Trouble Audible" is not to be programmed.
"Easy programming of Auto download ID #'s and PC Preset Callback" is not to be programmed.
"Sensor Watch" is not to be programmed.
GEM-P816 Installation Instructions
4-Wire
Smoke Detector
449AT
449CLT
712U
449C
449CSLT
722U
449CRT
449CTE
732U
449CST
741U
711U
449CSRT
742U
721U
449CSRH
721UT
449CSST
1112
2112T
2100
2112
2112TSRB
2100T
2-Wire
Smoke Detector
Smoke Detector *
731U
701U
702U
702RE
702RU
1100
WI994A 10/99
Base
NAPCO Security Systems