Table 9: Electrical Data
ZF180-240 - High Static Drive
Compressors
Size
Volt
(Tons)
RLA
C1
C2
380-3-50 18.6
14.5 100.0 90.5
180
(15)
415-3-50 18.6
14.5 111.0 101.0 26.0
380-3-50 20.7
20.0 110.0 110.0 29.0
240
(20)
415-3-50 20.7
20.0 118.0 118.0 29.0
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
OD Fan
Motors
(each)
(each)
LRA
MCC
FLA
C1
C2
C1
C2
26.0
20.3
2.1
20.3
2.1
28.0
2.1
28.0
2.1
Supply
Blower
Electric Heat Option
Motor
FLA
Model
kW
Stages
None
--
--
E18
11.3
1
6.3
E36
22.6
2
E54
33.8
2
E72
45.1
2
None
--
--
E18
13.5
1
6.7
E36
26.9
2
E54
40.0
2
E72
53.8
2
None
--
--
E18
11.3
1
8.2
E36
22.6
2
E54
33.8
2
E72
45.1
2
None
--
--
E18
13.5
1
9.1
E36
26.9
2
E54
40.0
2
E72
53.8
2
1061903-XIM-A-0713
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
Amps
--
49
60
17.1
49
60
34.3
51
60
51.4
73
80
68.6
90
100
--
49
60
18.7
49
60
37.4
56
60
56.2
79
80
74.9
84
90
--
60
70
17.1
60
70
34.3
60
70
51.4
75
80
68.6
96
100
--
60
70
18.7
60
70
37.4
60
70
56.2
82
80
74.9
87
90
17