Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
blower tables to select the blower speed and the BHP
requirement.
Solution: As in the example above, no temperature
information is given so 70°F is assumed.
Drive Selection
1.
Determine side or bottom supply duct application.
2.
Determine desired airflow
3.
Calculate or measure the amount of external static pressure.
4.
Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
5.
Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.
6.
Review the BHP compared to the motor options available. Select the appropriate motor and/or drive.
7.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8.
Determine turns open to obtain the desired operation point.
Example
1.
6800 CFM
2.
2.0 iwg
3.
Using the supply air blower performance table below, the following data point was located: 1020 RPM & 5.92 BHP.
4.
Using the RPM selection table below, Size X and Model Y is found.
5.
5.92 BHP exceeds the maximum continuous BHP rating of the 5.0 HP motor. The 7.5 HP motor is required.
6.
1020 RPM is within the range of the 7.5 HP drives.
7.
Using the 7.5 HP motor and drive, 3.5 turns open will achieve 1020 RPM.
Example Supply Air Blower Performance
Air Flow
0.4
0.6
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
5 HP & Field
Supplied
Drive
6400
719
2.55
756
3.03
6800
742
3.02
778
3.51
7200
765
3.54
802
4.03
7600
790
4.11
827
4.60
Table X: RPM Selection
Size
Model
HP
(Tons)
5
X
Y
7.5
Johnson Controls Unitary Products
Available External Static Pressure - IWG
0.8
1.0
1.2
Standard 5 HP & Drive
792
3.49
828
3.92
864
4.32
814
3.97
850
4.40
886
4.79
838
4.49
874
4.92
910
5.32
863
5.06
899
5.49
935
5.88
Max
Motor
Blower
BHP
Sheave
Sheave
5.75
1VP60
BK110
8.63
1VP60
BK090
The 1.5" static pressure given is at an elevation of 5,000 ft. The
first step is to convert this static pressure to equivalent sea level
conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
BHP at 5,000 ft. = 3.2 x .832 = 2.66
1.4
1.6
1.8
899
4.67
933
4.98
966
5.24
921
5.15
955
5.46
988
5.72 1020 5.92 1050 6.07 1078 6.15 1105 6.16
945
5.67
979
5.98 1012 6.24 1044 6.44 1074 6.59 1102 6.67 1129 6.68
970
6.24 1004 6.55 1037 6.81 1069 7.01 1099 7.16 1127 7.24 1154 7.25
6 Turns
5 Turns
4 Turns
Open
Open
Open
730
765
800
905
950
990
1061903-XIM-A-0713
2.0
2.2
2.4
High Static 7.5 HP & Drive
998
5.45 1028 5.59 1056 5.67 1083 5.68
7.5 HP & Field
Supplied Drive
3 Turns
2 Turns
1 Turn
Open
Open
Open
835
870
905
1035
1075
1120
2.6
Fully
Closed
N/A
N/A
27