Optional Gas Heat; Gas Application Data; Gas Pipe Sizing - Capacity Of Pipe; Gas Heat Minimum Supply Air Imperial - York ZF 180 Series Installation Manual

Hide thumbs Also See for ZF 180 Series:
Table of Contents

Advertisement

1061903-XIM-A-0713

Optional Gas Heat

These gas-fired heaters have aluminized-steel or optional
stainless steel, tubular heat exchangers with spark ignition with
proven pilot.
Table 13: Gas Application Data
Unit
Input
Size
Opt.
(MBH)
24
180
32
24
240
32
Gas Piping
Proper sizing of gas piping depends on the cubic feet per hour
of gas flow required, specific gravity of the gas and the length of
run. "National Fuel Gas Code" Z223.1 (in U.S.A.) or the current
Gas Installation Codes CSA-B149.1 (in Canada) should be
followed in all cases unless superseded by local codes or gas
utility requirements. Refer to the Pipe Sizing Table 13. The
heating value of the gas may differ with locality. The value
should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specifying
a minimum diameter for gas piping. All units require a
one-inch pipe connection at the entrance fitting.
Main
Manual
Shut-off
Valve
Figure 16: External Supply Connection External Shut-Off
20
Temp Rise
Output (MBH)
300
240
400
320
300
240
400
320
Drip Leg
(°F)
20-50
30-60
20-50
30-60
Figure 17: Bottom Supply Connection External Shut-Off
Table 14: Gas Pipe Sizing - Capacity of Pipe
Length of
Pipe ft. (m)
10 (3)
20 (6)
30 (9.1)
40 (12.1)
50 (15.2)
60 (18.2)
70 (21.3)
80 (24.3)
90 (27.4)
100 (30.4)
NOTE: Maximum capacity of pipe in cubic feet of gas per hour
based upon a pressure drop of 0.3 inch W.C. and 0.6
specific gravity gas.
Table 15: Gas Heat Minimum Supply Air Imperial
Size
(Tons)
180
(15)
240
(20)
Table 16: Gas Heat Minimum Supply Air Metric
Size
(Tons)
180
(15)
240
(20)
Drip Leg
Nominal Iron Pipe Size
1 in.
1-1/4 in.
520 (14.7)
1050 (29.7)
350 (9.9)
730 (20.6)
285 (8)
590 (16.7)
245 (6.9)
500 (14.1)
215 (6)
440 (12.4)
195 (5.5)
400 (12.4)
180 (5)
370 (10.4)
170 (4.8)
350 (9.9)
160 (4.5)
320 (9)
150 (4.2)
305 (8.6)
Supply Air (CFM)
Heat Size
Cooling
Min
Max
24
4500
7000
32
4500
7000
24
6000
9400
32
6000
9400
Supply Air (M
Heat Size
Cooling
Min
Max
24
2.13
3.3
32
2.13
3.3
24
2.83
4.44
32
2.83
4.44
Johnson Controls Unitary Products
Main
Manual
Shut-off
Valve
Heating
Min
Max
4500
7000
4500
7000
6000
9400
6000
9400
3
/S)
Heating
Min
Max
2.13
3.3
2.13
3.3
2.83
4.44
2.83
4.44