Meaning
Blockage detected on high pressure pipe
Reverse phase or open phase
Heating operation restricted at outdoor temperature over
Theat_high value (default: 30 °C)
Cooling operation restricted at outdoor temperature below
Tcool_low value (default: 0 °C)
Fan speed error
Error due to operation failure of inverter compressor
System stop due to full current control
Over current trip / PFC over current error
IPM Over Current(O . C )
Comp . Over load error
DC-Link voltage under/over error
Error due to abnormal rotation of the compressor or
unconnected wire of compressor
Error on current sensor (Short or Open)
Error on DC-Link voltage sensor (Short or Open)
Outdoor unit EEPROM Read/Write error (Option)
Outdoor unit EEPROM Read/Write error (H/W)
AC Line Zero Cross Signal out
Comp Lock error
Error on IPM Heat Sink sensor of inverter 1 (Short or Open)
Error on inverter fan 2
Remarks
1 . Check if the service valve is
open
2 . Check for refrigerant
leakage(pipe connections,
heat exchanger) and charge
refrigerant if necessary
3 . Check if there's any blockage
on refrigerant cycle(indoor
unit/outdoor unit)
4 . Check if additional
refrigerant has been added
after pipe extension
Check whether 3 phase is
reversed or opened .
HEATING
COOLING
FAN1 ERROR
-
-
Check OLP sensor
IPM
-
Check AC Power and DC Link
Voltage
Check Comp wire
Check Outdoor Inverter PBA .
-
Check Outdoor EEPROM Data
Check Outdoor EEPROM PBA
-
-
Check Outdoor Inverter PBA .
FAN2 ERROR