APPENDIX A
APPENDIX A COMMISSIONINGA.1 COMMISSIONING
DESCRIPTION
DEFAULT
SETPOINTS
PF TRIP
–0.60
PF DELAY
1.0 s
PF SUPP
6% FLC
PF MODE
ridethru
FAR DELAY
0 s
FCX DELAY
1 s
AC CT RTG
50/5
FL AMPS
25
LR AMPS
200
SYNC SLIP
5.0%
STALL TIME
10 s
RUNTIME
1.05 x ST
DC CT PRIM
5 A
HIGH FIELD
OFF
FIELD AMPS
OFF
FLD IE DLY
N/A
FIELD VOLTS
OFF
EX VLT DELAY
N/A
INC SEQ DLY
OFF
REG PF
0.00
REG GAIN
1
STABILITY
1 cyc
REG OUTPUT
1 V
FLOOR VOLTS
0.0
GE Power Management
USER VALUE
SPM Synchronous Motor Protection & Control
A.1.1 COLLECTOR-RING SETTINGS
DESCRIPTION
DEFAULT
CONFIGURATIONS
MOTOR
Coll-Ring
LINE FREQ
60 Hz
PF REF
internal
RTU ADDRESS
1
BAUD RATE
19.2k
PARITY
None
TURNAROUND
5
STAT
read only
PASSWORD
0000
CALIBRATION
FS EXC VOLT
FS EXC AMPS
FS MTR AMPS
A.1 COMMISSIONING
USER VALUE
A-
1
A