GE SPM Series Instruction Manual page 100

Synchronous motor protection and control
Table of Contents

Advertisement

9.2 MEMORY MAPPING
Table 9–2: MODBUS MEMORY MAP (Sheet 3 of 5)
GROUP
ADDR
(hex)
DIGITAL
024C
INPUTS
024D
024E
0254
STATISTICS
0255
(can be written
0256
as holding
0257
registers)
0258
0259
025A
025B
025C
025D
025E
025F
0FFF
Setpoints (Holding registers at addresses 1000 to 2FFF)
SYSTEM
1000
CONFIGURATION
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
104F
9
*
Range for collector-ring motors.
** Range for brushless motors.
1. The access password must be written correctly before any setpoints can be written via Modbus. The password is initially the same as the default password,
but the two passwords are stored separately, so the keyboard can not be used to change the communications password and vice-versa.
2. The allowable range of FLA is as follows: the minimum full load amps value is 2/5 times the CT ratio; the maximum is equal to the CT ratio.
3. The locked rotor current is range dependent on the FLA setpoint: the minimum is twice the full load amps and the maximum value is 12 times the FLA.
4. REGULATOR OUTPUT must be greater than or equal to FLOOR VOLTS, likewise FLOOR VOLTS must be less than or equal to REGULATOR OUTPUT.
9-
4
DESCRIPTION
MX Status
NX Status
Reserved
Reserved
Motor Running Hours
Incomplete Sequence Trip Counter
Field Loss Trip Counter
Pull Out Trip Counter
Resynchronization Trip Counter
Missing External PF Voltage Reference
Check Exciter Trip Counter
Power Factor Trip Counter
Squirrel Cage Trip Counter
Field Overtemperature Trip Counter
Reserved
Reserved
1
ACCESS PASSWORD
MOTOR TYPE
LINE FREQUENCY
POWER FACTOR REFERENCE
RTU ADDRESS
BAUD RATE
RS485 PARITY
RS485 MIN. TURNAROUND TIME
STATISTICS MODE
NEW PASSWORD
Reserved
Reserved
SPM Synchronous Motor Protection & Control
9 MODBUS COMMUNICATIONS
RANGE
STEP
UNITS
VALUE
0 to 9999
1
0 or 1
-
0 or 1
-
Hz
0 or 1
-
1 to 254
1
0 to 9
1
baud
0 to 2
1
0
1000
ms
0 or 1
1
0 to 9999
1
FORMAT
FACTORY
CODE
DEFAULT
Switchstate
N/A
Switchstate
N/A
U16
N/A
U16
N/A
U16
N/A
U16
N/A
U16
N/A
U16
N/A
U16
N/A
U16
N/A
U16
N/A
U16
N/A
-
U16
0000
-
Motortype
0
Linefreq
0
-
PFreg
1
-
U16
1
Baudrate
6
Parity
0
U16
5
-
Startmode
1
-
U16
4985
GE Power Management

Hide quick links: