Installation - Honeywell DG T Series Operating Instructions Manual

Pressure switches for gas

Advertisement

Type label
For detailed information on the adjusting range, mean
switching differential, max. inlet pressure, lock-off,
medium and switching properties, see page  5
(Technical data) and the table on page  3 (Ad-
justment).

Installation

CAUTION
Please observe the following to ensure that the
DG..T is not damaged during installation and op-
eration:
Continuous operation with gases containing
more than 0.1 %-by-vol. H
centrations exceeding 200 µg/m
the ageing of elastomer materials and reduce
the service life.
Use approved sealing material only.
Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
Check max. ambient temperature  – see
page 5 (Technical data).
When using silicone tubes, only use silicone
tubes which have been sufficiently cured.
Vapours containing silicone can adversely affect
the functioning of electrical contacts.
Condensation or vapours containing silicone
must not be allowed to get into the housing.
At subzero temperatures, malfunctions/failures
due to icing can occur.
When installing outdoors, place the DG..T in
a roofed area and protect from direct sunlight
(even IP 65 version).
Avoid strong impact on the unit.
▷ Installation position as required, preferably with
vertical diaphragm. Then the switching point p
corresponds to the scale value SK set on the
hand wheel. In other installation positions, the
switching point p
S
correspond to the scale value SK set on the
hand wheel. Check the switching point.
p s = SK
p s =SK + 0,08 "WC
Approval and type: see
type label.
S or ozone con-
2
3
accelerate
will change and no longer
p s = SK - 0,08 "WC
CAUTION
If port 4 is at the top, IP 65 will not be satisfied.
▷ The DG..T must not be in contact with masonry.
Minimum clearance 1" (25 mm).
▷ Ensure that there is sufficient installation space.
▷ Ensure unobstructed view of the hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
3 Ensure that the pipeline is clean.
Ports
4
1
2 *
Positive
pressure
DG..T
Negative
pressure
DG..T
Differential
1 or 2* for higher absolute pressure.
pressure
4 for lower absolute pressure.
DG..T
* Port 2 only on DG..T..2 with 2x ¼" NPT connections..
CAUTION
Port 4 connects the upper diaphragm chamber
with the micro switch. Do not connect port 4 to
pipes carrying gas.
▷ The pressure switches are supplied with an inte-
grated vent limiter. In the event of a diaphragm
tear, the vent limiter limits the escape of gas
to less than 1.0 CFH of natural gas at 2.8 psi
(DG..6T) or 7 psi (DG..10T – DG..500T). If neces-
S
sary, port 4 (1/8" NPT) can be used to connect
the venting line.
▷ A filter pad at port 4 protects the electrical contacts
in the DG..T from dirt particles in the surrounding
air or in the medium.
▷ Filter pad for port 4, see PartDetective.
USA-2
4
IP 65
1 or 2 for
positive pressure (¼" NPT)
4 for
negative pressure (
/
" NPT)
1
8
Connect
Free
1 or 2*
4
4
1 or 2*