Operating instructions
Pressure switches for air
DL..A, DL..K
Cert. version 05.18
Safety
Please read and keep in a safe place
Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the opera-
tor. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
• , 1 , 2 , 3 ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-com-
pliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
E
DK
S
N
P
GR
www.docuthek.com
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Changes to edition 05.18
The following chapters have been changed:
Checking the usage
Installation
Accessories
Technical data
Certification
Checking the usage
DL 1,5 – 3A, DL 3K, DL 5 – 150A, DL 5 – 150K
For monitoring positive, negative or differential pres-
sures of air, flue gas or other non-aggressive gases.
This function is only guaranteed when used within
the specified limits – see page 5 (Technical data).
Any other use is considered as non-compliant.
Type code
Code
DL
1,5 – 150
With tube connection and hand wheel
K
A
Additionally with Rp ¼ connection
T
G
-2
-3
-4
-5
-6
-9
K2
Red/green pilot LED for 24 V DC/AC
T
T2
Red/green pilot LED for 230 V AC
N
P
1
With 1 test key (lower chamber +)
2
With 2 test keys (upper chamber -,
A
W
Part designations
2
1
Upper housing section with cover
2
Lower housing section
3
Hand wheel
4
M16 cable gland
GB-1
Description
Pressure switch for air
Max. setting in mbar
(optional: Rp
T-product
Gold contacts
Electrical connection
via screw terminals, 1/2" NPT
via screw terminals
via screw terminals, IP 65
4-pin plug, without socket
4-pin plug, with socket
4-pin plug, with socket, IP 65
Blue pilot lamp for 230 V AC
Blue pilot lamp for 120 V AC
With test tapping point
lower chamber +)
External adjustment
Z-angle bracket
2
1
/
)
1
8
3
4

Advertisement

loading

Summary of Contents for Honeywell Krom Schroder DL A Series

  • Page 1 Conversion, spare parts 34425501 All technical changes are prohibited. Only use OEM spare parts. www.docuthek.com   Changes to edition 05.18 Operating instructions Pressure switches for air The following chapters have been changed: DL..A, DL..K – Checking the usage – Installation –...
  • Page 2: Installation

    ▷ Installation in the vertical or horizontal position, or Type label upside down, preferably with vertical diaphragm. If installed in a vertical position, the switching D-49018 Osnabrück, Germany point p will correspond to the scale value SK. ▷ If installed in another position, the switching point p will change and no longer correspond Max.
  • Page 3: Differential Pressure Measurement

    (0.14" × 0.3") Positive pressure measurement 54,5 (2.1") 2,7 × 16 DL 5–150K (0.11" × 0.6") 45 (1.77") 25 (0.98") 64 (2.5") 45 (1.8") ▷ 1 or 2 = positive pressure port (+). ▷ If port 2 is used, close off port 1. ▷...
  • Page 4 Adjustment C = 1 µF R = 22 ▷ The switching point is adjustable via hand wheel. 1 Disconnect the system from the electrical power supply. 2 Detach the housing cover, see page 5 (Tech- nical data). 1 Disconnect the system from the electrical power 3 Connect an ohmmeter.
  • Page 5: Function Check

    ▷ Deviation from the switching point during testing Mechanical data pursuant to EN 1854: Max. inlet pressure = withstand pressure: see type Air pressure switches: label or page 4 (Adjustment). Diaphragm pressure switch, NBR, silicone-free. Deviation DL 5 – 150A, Housing: glass fibre reinforced PBT plastic with ±...
  • Page 6 The addresses are Elster GmbH available on the Internet or from Elster GmbH. Strotheweg 1, D-49504 Lotte (Büren) Tel. +49 541 1214-0 We reserve the right to make technical modifications Fax +49 541 1214-370 in the interests of progress. hts.lotte@honeywell.com, www.kromschroeder.com GB-6...