System Configuration 12 - Wolf COB-2 Operation Instructions Manual

Oil condensing boiler for central heating with stratification cylinder
Table of Contents

Advertisement

Appendix
BSP cylinder with header sensor
Fig. 12.8
System configuration 11 - BSP cylinder with header sensor
Input: Cylinder temperature sensor
q
Input E2: Header temperature sensor
w
Cylinder primary pump
e
– Burner starts subject to demand from the header temperature control (heating mode) or in case of
cylinder demand.
– Feed/heating circuit pump enabled as a feed pump (heating mode only). Not activated during cylinder
heating.
– Header temperature control (heating mode only)
– Input E2: Header sensor (heating mode only)
– In case of cylinder heating, the reference temperature is provided by the boiler sensor.
– Heating circuit with MM-2! see hydraulic schemes no. 16-52-018-003, 16-52-018-005 and
16-52-018-006
12.3.4
System configuration 12
Low loss header with header sensor + direct heating circuit (A1)
Fig. 12.9
System configuration 12 - Low loss header with header sensor
Input E2: Header temperature sensor
q
Feed/heating circuit pump
w
Header temperature sensor
e
– Burner starts subject to demand from the header temperature control
– Feed/heating circuit pump enabled as a feed pump for header demand
– Header temperature control
– Input E2: Header sensor
– Parameter 08 (T-Flowmax): 90°C
– Parameter 22 (max. boiler temp.): 90°C
– Parameter 14 (output A1): HCP
3066501_201910
e
q
w
r
Feed/heating circuit pump
r
Cylinder temperature sensor
t
Header temperature sensor
y
q
w
e
r
A1 = heating circuit pump
r
Direct heating circuit
t
t
y
t
WOLF GmbH | 85