Combined Venting - State Water Heaters SANDBLASTER SBD30 150 Service Handbook

Self-cleaning induced draft multi flue commercial gas water heaters
Hide thumbs Also See for SANDBLASTER SBD30 150:
Table of Contents

Advertisement

SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL

COMBINED VENTING

COMBINING VENTS (MANIFOLDING
When vents are combined, the area of the
combined vent should be equal to area of
the largest single vent, plus 50% of area of
all others joining.
EXAMPLE: To combine two 6" vents with
an 8" vent, the area of a combined vent
should be one half area of two 6 inch vents
(14 + 14) plus area of 8 inch vent (50)
or 78 sq. inches.
Referring to chart: 78 sq. inches requires
a 10" diameter vent.
Maximize height from water heater vent connection to first elbow or tee.