5.6
Process times
The 'Set process times' menu is used to set relevant times for the battery-charging mode.
5.6.1
Set switch back time
This is a sub-item of the 'Set process times' menu and is used to set the length of time for
secondary battery charging. This time begins as soon as the battery's charging current drops below
2.5A. After this, the MultiCharger 1500 stays on charge until the expiry of the switch back delay set
here. It then switches to trickle charge.
Default setting: 120 minutes
5.6.2
Set maximum charging time
This is a sub-item of the 'Set process times' menu and is used to set maximum time for battery
charging. If the battery's charging current does not drop below 2.5A, charging then stops at the end of
the maximum charging period that you have entered here.
Default setting: 10 hours
5.6.3
Set current limit 2
This is a sub-item of the "Set process times" menu. If the charging current of the battery sinks under
current limit 2, the signals (LEDs on the display or signal lamps) change from yellow to green.
The charging process is not interrupted and the LC display continues to signal the current charging
status.
Default setting: 8.0A
Setting range: 0 – 999 minutes
Setting range: 0 – 24 hours
Setting range: 0...20A