5.4
Set voltage limit
The 'Set voltage limit' menu is used to set monitoring limits for overvoltage and undervoltage.
5.4.1
Set Ua max 12V
This is a sub-item of the 'Set voltage limit' menu and is used to set the monitoring limit for
overvoltage where output voltage is 12V.
Default setting: 16.0V
5.4.2
Set Ua min 12V
This is a sub-item of the 'Set voltage limit' menu and is used to set the monitoring limit for
undervoltage with output voltage at 12V.
Default setting: 7.0V
5.4.3
Set Ua max 24V
This is a sub-item of the 'Set voltage limit' menu and is used to set the monitoring limit for
overvoltage with output voltage at 24V.
Default setting: 32.0V
5.4.4
Set Ua min 24V
This is a sub-item of the 'Set voltage limit' menu and is used to set the monitoring limit for
undervoltage with output voltage at 24V.
Default setting: 14.0V
Setting range: 15.0V – 16.0V
Setting range: 7.0V – 10.0V
Setting range: 30.0V – 32.0V
Setting range: 14.0V – 20.0V
Page 28