Appliance
Automatic heating device, heat
transfer by means of infrared dark
radiation.
Fuel Types
Natural gas
Propane
Minimum connection pressure in front of valve
Gas type
Natural Gas H
Natural Gas L
Propane
Attention!
Max. connection pressure: 65 hPa
Gas connection 15-35 kW
50-60 kW
[Connection fitting ¾"enclosed in burner kit
cardboard]
deltaSchwank 310U / 320U
Fig 16: Dimension deltaSchwank 310U / 320U
[view from below]
Fig 17: Dimension deltaSchwank 625U / 635U
[view from below]
20
310 – 1260U
15 hPa
20 hPa
40 hPa
R=1/2'' male
R=3/4" male
Electrical connection power supply
Single-phase AC 230 V, N, PE - 50Hz
The connecting cable for the power supply is
connected to the IC 4000/1 burner control with
the provided 4-pin plug.
The power supply for the heater must be flexible
with maximal wire cross-section
- 3x 1.5 mm
Ölflex- or silicone cable
2
To set the bluTek-burner kit free of voltage it is
only necessary to remove the plug of the power
supply.
Regulation
The heating system is controlled via the central
control unit SchwankControl Touch.
The corresponding heating commands for the
heater are sent via MODBUS.
Connection MODBUS control from
SchwankControl Touch to IC 4000/1
Use for MODBUS transmission max. 3x 0.5 mm
cable.
Route the cable through the lower cable gland
into the housing of burner control unit IC 4000/1
and connected to the corresponding spring
terminals on the circuit board.
Exhaust gas connection
Flange at radiant tube end for exhaust
connection Ø 100 [flexible stainless steel pipe /
exhaust gas adapter]
deltaSchwank 625U / 635U
2