wiring terminal is rated to 105˚C and accepts a maximum of 16 mm
AWG) wire.
Circuit Rating
80 A
70 A
60 A
Determine the plug type purchased by the
3.
homeowner. It is either a NEMA 6-50 or 14-50 type
plug.
Determine if the desired circuit rating requires a
4.
hardwired circuit.
Ensure the electrical panel supports a 240 V dedicated circuit with a
5.
new, dedicated, two-pole circuit breaker.
For plug-in installation, use a GFCI circuit breaker.
For a hardwired installation, use a non-GFCI circuit breaker.
For plug-in installations, the NEMA
6.
outlet should be located 500-660 mm
(20-26 in) from the ground adjacent to
the stud where the charging station will
be mounted.
The input power cable is 300 mm
Note:
(12 in) long (as per the National Electric
Code for EV chargers). Ensure the outlet
is installed close enough to the stud for
the input power cable to plug in.
Follow all applicable codes and
7.
ordinances and pull a permit for
completing the electrical work as
required.
10 chargepoint.com
Max Load
Estimated Range per Hour Plug-in
50 A
37 miles/60 km
50 A
37 miles/60 km
48 A
36 miles/58 km
no
no
no
14-50
300 mm
(12 in)
500-600 mm
(20-26 in)
2
(6
Hardwire
yes
yes
yes
6-50