Carel IR32M Manual page 46

Table of Contents

Advertisement

Models
Programming
Keypad
Remote commander (optional)
Mechanical characteristics
Dimensions:
33 x 75 x 72:
33 x 75 x 64:
Index of protection: IP65 (front panel)
IP40 (front panel)
Stirrup-catch fixing:
Quality and accuracy
Test in circuit
Watch dog
Immunity from interference according to standards
IEC 801-2 and 801-4 level 4
GENERAL SPECIFICATIONS (for all models)
Connection
Classification according to protection against shock
Number of automatic cycles for each automatic action (e.g.: relay)
Ageing period (operating hours)
Type of action-disconnection
PTI of materials used for insulation
Period of electric stress across insulating parts
Environmental pollution
Heat and fire resistance category
Category (surge immunity)
Software class and structure
Time constant
Disposal of the product
Electrical characteristics of relays fitted in all models except the
compressor relay on board S90RDPW200
Maximum peak current: 10A
Maximum operating current: 8A
Maximum operating power: 2000VA
Maximum operating resistance load at 220Vac: 1760W
Maximum inductance load 300 W at 220Vac (cos.psi=0.7)
Maximum operating tension: 250Vac
IR32M
IR32S
IRDRS0
Screw terminals for cables with min. 0.5mm
Class I
100.000
60.000
1C
250 V
Long
Normal
D
1
Class A (EN60730-1)
35 s in forced air
avoid disposing the device in domestic rubbish. To dispose the device
environmental protection laws in force in your Country
Electrical characteristics of the compressor relay fitted on board S90RDPW200
Maximum peak current: 70A
Maximum operating current: 20A
Maximum operating power: 5000VA
Maximum operating resistance load at 220Vac: 4400W
Maximum inductance load 1800 W at 220Vac (cos.ϕ=0.7)
Maximum operating tension: 250Vac
45
IRDRSE
IR32Y
IR32P
2
2
- max. 1,5mm
cross-section
IR32C
IRDRC
refer to the
Cod. +030220151 - Rel. 2.1 - 04/09/98