fault code list.

3-4. Audible Alarm

Description
UPS status
Bypass mode
Battery mode
Fault mode
Warning
Overload
Others
Fault
All

3-5. Single UPS Operation

1. Turn on the UPS with utility power (in AC mode)
1) After power mains is connected correctly, set the breaker of the battery pack to "ON" position (this
step only necessary for long-run model). Then set the line input breaker to "ON" position. At the
same time the fan will start running and the UPS will start initialization. In just a few seconds, the
UPS will supply power to the loads via the Bypass mode.
NOTE: When UPS is in Bypass mode, the output voltage will be directed from mains after you switch
on the input breaker. In Bypass mode, the load is not protected by the UPS. To protect your precious
devices, you should turn on the UPS. Refer to next step.
2) Touch "CONTROL" and select "UPS on/off" icon. It will show "Turn on UPS?" in screen and select
"Yes". Refer to On/Off UPS screen.
3)
In just a few seconds, the UPS will enter into AC mode. If the mains is abnormal, the UPS will
operate in Battery mode without interruption.
NOTE: When the UPS runs out battery, it will shut down automatically in Battery mode. When the mains
is normalized, the UPS will auto restart in AC mode.
2. Turn on the UPS without utility power supply (in Battery mode)
1) Make sure that the two strings of batteries are connected correctly in order of "+,GND,-" terminals
and the breaker of the battery pack is at "ON" position (only for long-run model).
2) Press the "
mode. After initialization, UPS will enter to "No Output mode"
3) In just a few seconds, the UPS will be turned on and enter into Battery mode.
20KVA
Bypass Mode
Date Time
CODE
2018/11/8
17:02:30
01
2018/11/8
17:02:30
02
HOME
CONTROL
MEASURE
" button to set up the power supply for the UPS. UPS will enter to power on
TYPE
Description
Mode
Bypass Mode
Mode
Standby Mode
SETTING
INFO
Data Log Page
Buzzer status
Beeping once every 2 minutes
Beeping once every 4 seconds
Beeping continuously
Beeping twice every second
Beeping once every second
Beeping continuously
32
19:52:36
2018-11-07
DATALOG
.
Muted
Yes
No
Yes