Battery Backup Power 15KL Manual page 30

Dual online ups
Table of Contents

Advertisement

ELECTRICAL
Output Voltage: Select the output rated voltage.
There are two options, 120V and 127V. 120Vac is default setting.
Output Rated FRE: Select output rated frequency.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of "Output Freq.". The input frequency could be from 40Hz to 70Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with the bypass
frequency within 45~55 Hz for 50Hz system or within 55~65 Hz for 60Hz system. Disable is the
default setting.
Bypass Forbid:
Enable: Bypass Forbid is enabled. It's not allowed for running in Bypass mode under any
situations.
Disable: Bypass Forbid is disabled. UPS will run in Bypass mode. It is the default setting.
 Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only
available when "Bypass forbid" is set to "Disable".
Enable: Bypass enabled. When selected, bypass mode is activated.
Disable: Bypass disabled. When selected, no output through bypass when manually turning off
the UPS.
Bypass Voltage Range: Set the bypass voltage range.
L: Low voltage point for bypass. The setting range is 96V ~ 110V. 96V is default setting.
20KVA
Bypass Mode
OUTPUT VOL
OUTPUT FRE
ELECTRONIC
CVCF Mode
BATTERY
Bypass Forbid
MISCELLANEOUS
UPS SELFTEST
HOME
CONTROL
MEASURE
Electrical Setting Page 1
20KVA
Bypass Mode
Bypass UPS Off
Bypass VOL Range
ELECTRONIC
Bypass FRE Range
BATTERY
ECO Mode
MISCELLANEOUS
UPS SELFTEST
ECO VOL Range
ECO FRE Range
HOME
CONTROL
MEASURE
Electrical Setting Page 2
120V
60Hz
Disable
Disable
SETTING
INFO
Enable
96V
146V
56.0Hz
64.0Hz
Disable
115V
125V
58Hz
62Hz
SETTING
INFO
27
19:52:36
2018-11-07
DATALOG
19:52:36
2018-11-07
DATALOG

Advertisement

Table of Contents
loading

This manual is also suitable for:

15k dual15k20k20k dual20kl20kl dual

Table of Contents