BATTERY
Battery Warning Voltage:
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.1V ~ 14.0V. 11.4V is default setting.
This parameter setting is related to "Shutdown Voltage" setting. This setting value should be
higher than "Shutdown Voltage" setting.
Shutdown Voltage: If battery voltage is lower than this point in battery mode, UPS will automatically
shut down. The setting range is 10.0V ~ 12.0V. 10.7V is default setting. (The setting is only available
for long-run model)
Battery Parameter:
Battery AH: setting battery capacity. 9Ah is default setting.
MISCELLANEOUS
Auto Restart: (This function is reserved for future use)
Enable: After "Enable" is set, once UPS shutdown occurs due to low battery and then utility
restores, the UPS will return to line mode.
Disable: After "Disable" is set, once UPS shutdown occurs and the utility restores, the UPS will
not automatically turn on.
Shutdown Delay Min: UPS will shut down in setting minutes. The countdown will start after confirming
the pop-up screen.
Restore Delay Min: UPS will automatically restart in setting minutes after the UPS shuts down.
20KVA
Bypass Mode
BATT Warning VOL
Shutdown VOL
ELECTRONIC
BATT Age
BATTERY
BATT Parameters
MISCELLANEOUS
BATT AH
HOME
CONTROL
MEASURE
Battery setting page
20KVA
Bypass Mode
Auto Restart
Shutdown Delay
ELECTRONIC
Restore Delay
BATTERY
New Password
MISCELLANEOUS
HOME
CONTROL
MEASURE
Miscellaneous setting page
HIGH
14.4V
LOW
11.5V
10.7V
24
9
SETTING
INFO
Enable
0min
0min
****
SETTING
INFO
20
19:52:36
2018-11-07
DATALOG
19:52:36
2018-11-07
DATALOG

Advertisement

Table of Contents
loading

This manual is also suitable for:

15k dual15k20k20k dual20kl20kl dual

Table of Contents