Battery Backup Power 15KL Manual page 31

Dual online ups
Table of Contents

Advertisement

H: High voltage point for bypass. The setting range is 130V ~ 146V. 146V is default setting.
Bypass FRE Range: Set the bypass frequency range.
The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 50Hz system and from 56Hz to
64Hz when UPS is 60Hz system.
ECO mode: Enable/Disable ECO mode. Default setting is "Disable".
ECO Voltage Range: Set the ECO voltage range.
 L: Low voltage point for ECO mode. The setting range is from "Rated output voltage – 5V" to
"Rated output voltage - 11V". "Rated output voltage – 5V" is default setting.
 H: High voltage point for ECO mode. The setting range is from "Rated output voltage + 5V" to
"Rated output voltage + 11V". "Rated output voltage + 5V" is default setting.
ECO FRE Range: Set the ECO frequency range. The setting range is from 48Hz to 52Hz when the UPS
is 50Hz system and from 58Hz to 62Hz when the UPS is 60Hz system.
BATTERY
Battery Warning Voltage:
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.8V ~ 12.7V. 10.1V ~ 14.0V. 11.4V is
default setting. This parameter setting is related to "Shutdown Voltage" setting. The setting value
should be higher than "Shutdown Voltage" setting.
Shutdown Voltage: If battery voltage is lower than this point in battery mode, UPS will automatically
shut down. The setting range is 10.0V ~ 12.0V. 10.7V is default setting (The setting is only available for
long-run model)
Battery Parameter:
Battery AH: setting battery capacity. 9Ah is default setting.
MISCELLANEOUS
20KVA
Bypass Mode
BATT Warning VOL
Shutdown VOL
ELECTRONIC
BATT Age
BATTERY
BATT Parameters
MISCELLANEOUS
UPS SELFTEST
BATT AH
HOME
CONTROL
MEASURE
Battery setting page
20KVA
Bypass Mode
Auto Restart
Shutdown Delay
ELECTRONIC
Restore Delay
BATTERY
New Password
MISCELLANEOUS
DefaultUserPassword
UPS SELFTEST
HOME
CONTROL
Miscellaneous setting page
HIGH
14.4V
LOW
10.7V
24
9
SETTING
Enable
0min
0min
****
NO
MEASURE
SETTING
INFO
28
19:52:36
2018-11-07
11.5V
DATALOG
INFO
19:52:36
2018-11-07
DATALOG