default setting.
Bypass Forbid:
Allow: Bypass allowed. When selected, UPS will run in Bypass mode depending on "Byp.at off"
setting. It is the default setting.
Forbid: Bypass is not allowed. When selected, it's not allowed for running in Bypass mode under
any situations.
Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only
available when "Bypass forbid." is set to "Disable".
Enable: Bypass enabled. When selected, bypass mode is activated.
Disable: Bypass disabled. When selected, no output through bypass when manually turning off
the UPS.
Bypass Voltage Range: Set the bypass voltage range.
L: Low voltage point for bypass. The setting range is 96V ~ 110V. 96V is default setting.
H: High voltage point for bypass. The setting range is 130V ~ 146V. 146V is default setting.
Bypass FRE Range: Set the bypass frequency range.
The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 50Hz system and from 56Hz to
64Hz when UPS is 60Hz system.
ECO mode: Enable/Disable ECO mode. Default setting is "Disable".
ECO Voltage Range: Set the ECO voltage range.
 L: Low voltage point for ECO mode. The setting range is from "Rated output voltage – 5V" to
"Rated output voltage - 11V". "Rated output voltage – 5V" is default setting.
 H: High voltage point for ECO mode. The setting range is from "Rated output voltage + 5V" to
"Rated output voltage + 11V". "Rated output voltage + 5V" is default setting.
ECO FRE Range: Set the ECO frequency range. The setting range is from 46Hz to 54Hz when the UPS
is 50Hz system and from 56Hz to 64Hz when the UPS is 60Hz system.
20KVA
Bypass Mode
Bypass UPS Off
Bypass VOL Range
ELECTRONIC
Bypass FRE Range
BATTERY
ECO Mode
MISCELLANEOUS
ECO VOL Range
ECO FRE Range
HOME
CONTROL
MEASURE
Electrical Setting Page 2
Enable
96V
146V
56.0Hz
64.0Hz
Disable
115V
125V
58Hz
62Hz
SETTING
INFO
19