Parameter Information
Line Voltage Range: The acceptable line input voltage range.
Line FRE Range: The acceptable line input frequency range.
Bypass Voltage Range: The acceptable input voltage range for bypass mode.
Bypass FRE Range: The acceptable input frequency range for bypass mode.
ECO Voltage Range: The acceptable input voltage range for ECO mode.
ECO FRE Range: The acceptable input frequency range for ECO mode.
BATT Mode Work Time: The maximum discharge time in battery mode.
BATT Warning Voltage:
HIGH: High battery warning voltage.
LOW: Low battery warning voltage.
Shutdown Voltage: If battery voltage is lower this point, UPS will automatically shut down.
Shutdown Delay: UPS will shut down in setting minutes. The countdown will start after confirming the
pop-up screen.
Restore Delay: UPS will automatically restart in setting minutes after the UPS shuts down.
Battery Number: It shows battery number.
3-3-6. Data Log screen
Touch the icon
the UPS. The record contains date & time, code, type and description. Touch the icon
page up or down if there are more than one page in the date log. Touch the icon
screen. Press the icon
20KVA
Bypass Mode
Line VOL Range
Line FRE Range
BASIC
Bypass VOL Range
RATED
Bypass FRE Range
PARAMETER
ECO VOL Range
ECO FRE Range
HOME
CONTROL
Parameter Information Page 1
20KVA
Bypass Mode
BATTMode Work Time
BATT Warning VOL
BASIC
RATED
Shutdown VOL
PARAMETER
Shutdown Delay
Restore Delay
BATT Number
HOME
CONTROL
Parameter Information Page 2
to enter date log page. Data log is used to record the warning and fault information of
to go back to main menu. Please refer to Section 3-7 and 3-8 for warning and
80V
156V
56.0Hz
64.0Hz
96V
146V
56.0Hz
64.0Hz
115V
125V
58.0Hz
62.0Hz
MEASURE
SETTING
990Min
HIGH
14.4V
LOW
11.5V
10.7V
0min
0min
10
MEASURE
SETTING
31
19:52:36
2018-11-07
INFO
DATALOG
19:52:36
2018-11-07
INFO
DATALOG
to return to main
or
to