Laars MagnaTherm HTD Series Installation And Operation Instructions Manual page 46

Boilers and water heaters
Hide thumbs Also See for MagnaTherm HTD Series:
Table of Contents

Advertisement

Page 42
7.F Modbus and BACnet memory displays (continued)
Modbus
Address Type
R/W
48
U16
Read
49
U16
Read
50
U16
Read
51
S16
Read
52
S16
Read
53
S16
Read
54
S16
Read
55
U16
Read
56
U16
Read
64
Read
S16
65
U16
Read
66
Read
U16
67
U16
Read
68
Read
U16
69
U16
Read
70
Read
U16
71
U16
Read
72
Read
U16
73
U16
Read
74
Read
U16
75
U16
Read
76
Read
U16
77
U16
Read
78
Read
U16
79
U16
Read
80
Read
U16
81
U16
Read
82
S16
Read
83
U16
Read
84
U16
Read
Map Descriptor Name
History - Boiler Pump Cycles
History - DHW Pump Cycles
History - System Pump Cycles
History - Average Boiler Outlet Temperature
History - Maximum Boiler Outlet Temperature
History - Minimum Boiler Outlet Temperature
History - Boiler Average Firing Temperature
History - Boiler Maximum Firing Time
History - Boiler Minimum Firing Time
Modulation sensor
Lead Lag (Cascade) active service
Lag 1 State
Lag 1 Firing Rate
Lag 2 State
Lag 2 Firing Rate
Lag 3 State
Lag 3 Firing Rate
Lag 4 State
Lag 4 Firing Rate
Lag 5 State
Lag 5 Firing Rate
Lag 6 State
Lag 6 Firing Rate
Lag 7 State
Lag 7 Firing Rate
Lead 0 State
Lead 0 Firing Rate
Lead Firing Rate
Active CH Setpoint
Burner Status 1
LAARS Heating Systems
BACnet
BACnet
Data Type
Object ID Read/Write
AI
48
Read
AI
49
Read
AI
50
Read
AI
51
Read
AI
52
Read
AI
53
Read
AI
54
Read
AI
55
Read
AI
56
Read
0 = None
1 = Outlet
2 = DHW
AI
64
Read
3 = System
4 = Inlet
5 = Flue
6 = System Return
AI
65
Read
0 = Not Present
1 = Not Available
AI
66
Read
2 = Available
3 = Running
4 = Locked Out
AI
67
Read
Current firing rate (0-100%)
0 = Not Present
1 = Not Available
AI
68
Read
2 = Available
3 = Running
4 = Locked Out
AI
69
Read
Current firing rate (0-100%)
0 = Not Present
1 = Not Available
AI
70
Read
2 = Available
3 = Running
4 = Locked Out
AI
71
Read
Current firing rate (0-100%)
0 = Not Present
1 = Not Available
AI
72
Read
2 = Available
3 = Running
4 = Locked Out
AI
73
Read
Current firing rate (0-100%)
0 = Not Present
1 = Not Available
AI
74
Read
2 = Available
3 = Running
4 = Locked Out
AI
75
Read
Ccrrent firing rate (0-100%)
0 = Not Present
1 = Not Available
AI
76
Read
2 = Available
3 = Running
4 = Locked Out
AI
77
Read
Ccrrent firing rate (0-100%)
0 = Not Present
1 = Not Available
AI
78
Read
2 = Available
3 = Running
4 = Locked Out
AI
79
Read
Current firing rate (0-100%)
0 = Not Present
1 = Not Available
AI
80
Read
2 = Available
3 = Running
4 = Locked Out
AI
81
Read
Current firing rate (0-100%)
AI
82
Read
Current firing rate of the Cascade Lead (0-100%)
AI
83
Read
0=None
5 = Start
24 = Error Block
160 = Standby
165 = Check Safety Swtich
166 = Run
177 = Prepurge Open
181 = Parameter Block
183 = Lockout
AI
84
Read
188 = Testmode
194 = Prepurge Closed
195 = Wait for HIS Free
196 = HIS Preheat/Prespark
200 = Verify Primary SF
Notes