Laars MagnaTherm HTD Series Installation And Operation Instructions Manual page 124

Boilers and water heaters
Hide thumbs Also See for MagnaTherm HTD Series:
Table of Contents

Advertisement

Page 120
Condition
Information
Flow Switch
Insufficient flow at the outlet of the
boiler/heater
Auto-reset Condition
Annunciation – "Warning Flow switch open"
on Message Screen
Low Water
Insufficient water level in the boiler/heater
Outlet
Dual element sensor readings do not
Cut Off
heat exchanger.
Sensor Drift
agree.
Manual-reset Condition
Manual-reset Condition
Annunciation – on Navigation Bar
or
Annunciation – on Navigation Bar
Lockout: Low Water Cut Off
Flue
Sensor Drift
Manual
Outlet water temperature has exceeded the
Reset High
manual reset high limit setting
Limit
Manual-reset Condition
Annunciation – on Navigation Bar
Lockout: Man Reset High Limit
Auto Reset
Outlet water temperature has exceeded the
High Limit
auto reset high limit setting
Auto-reset Condition
Annunciation – "Warning High limit auto
error" on Message Screen
Inlet Sensor
Inlet sensor is damaged or not connected.
Pressure
Pressure transmitters are not measuring the
Manual-reset condition
Transmitter
same values.
Annunciation – on Navigation Bar
Lockout: Air Pressure Drift Error
Pressure
Pressure not within bounds
Transmitter
Lockout: Burner AN Pressure ERR
High Gas
The high gas pressure switch has tripped
Pressure
Manual-reset Condition
Burner
Sensing flame on burner prior to ignition.
Annunciation – on Navigation Bar
Parasitic
Manual-reset Condition
Lockout: High Gas Pressure
Flame
Annunciation – on Navigation Bar
Low Gas
The low gas pressure switch has tripped
Pressure
Manual-reset Condition
Burner Max
The maximum attempts for ignition has
Annunciation – on Navigation Bar
Trials
occurred, without sensing flame.
Lockout: Low Gas Pressure
Manual-reset Condition
Annunciation – on Navigation Bar
Condensate
Condensate trap water level is high
Level
Auto-reset Condition
Annunciation – "Warning Condensate level"
Additional
Outlet water temperature has exceeded the
on Message screen
High Limit
additional high limit setting
Outlet
Outlet probe is not connected
Auto-reset Condition
Sensor
Manual-reset Condition
Annunciation – "Warning Additional high
Annunciation – on Navigation Bar
limit" on Message Screen
Lockout: Outlet Probe
Lockout: Outlet Probe Drift
Lockout: Flue Probe Drift
Lockout: Inlet Probe
Lockout: Burner Parasitic Flame
Lockout: Burner Max Trials
LAARS Heating Systems
Corrective Action
Faulty boiler/heater pump – replace pump.
140
Faulty pump contactor – replace contactor.
158
Blown boiler/heater pump fuse – replace fuse F14 on the
176
control board.
194
212
Reset the LWCO from the reset button on the LWCO module.
Check the sensor and wiring. Repair or replace as needed.
Verify the system is full of water and all air has been purged
The outlet probe is a dual element probe with 10K and 20K
from the system.
thermistors. A quick test is to measure resistance and verify
Check for loose jumpers if the LWCO is not installed.
one resistance is double the other. Replace if necessary.
Measure the resistance of each element of the sensor and
compare to the resistance table below. Replace if necessary.
Verify the system is full of water and all air has been purged
from the system.
Resistance (Ω)
Temp (°F)
Verify the boiler/heater is piped properly into the heating
68
system.
86
Check for proper pump operations.
104
Check the manual reset high limit set point.
122
Verify the system is full of water and all air has been purged
140
from the system.
158
Verify the boiler/heater is piped properly into the heating
176
system.
194
Check for proper pump operations.
212
Check the manual reset high limit set point.
Check the sensor and wiring. Repair or replace as needed.
Check the wiring connections at transmitters and BIC (x122)
Measure the resistance of the sensor and compare to the
VCC to Ground should equal 5 Volts.
resistance table below. Replace if necessary.
Check pressure levels on Analog IN screen. Replace faulty
transmitter.
Temp (°F)
Temp (°C)
Check that pressure sense lines are not kinked or
68
disconnected.
86
Check that inlet and exhaust ducts are not blocked.
104
Check that blower is rotating during pre-purge.
122
Check wiring connections at transmitters and BIC (x22).
140
Check that pressure sense lines are not kinked or
158
disconnected.
176
194
Refer to Section 3 for Gas Supply and Piping information.
212
Verify supply and manifold gas pressures satisfy installation
Inspect flame and wiring for damage and continuity. Replace if
requirements.
necessary.
Refer to Section 3 for Gas Supply and Piping information.
Verify supply and manifold gas pressures satisfy installation
Verify supply and manifold gas pressures satisfy installation
requirements.
requirements.
Verify the proper intake and venting.
Inspect the burner.
Check pilot and main valve wiring and operation.
Check condensate trap for proper drainage
Check ignition transformer electrode, flame detector wiring and
Check condensate trap for stuck level switch
position.
Verify the system is full of water and all air has been purged
from the system.
Check the sensor and wiring. Repair or replace as needed.
Verify the boiler/heater is piped properly into the heating
The outlet probe is a dual element probe with 10K and 20K
system.
thermistors. A quick test is to measure resistance and verify
Check for proper pump operations.
one resistance is double the other. Replace if necessary.
Check the additional high limit set point.
Measure the resistance of each element of the sensor and
compare to the resistance table below. Replace if necessary.
Resistance (Ω)
Temp (°F)
68
86
104
122
2463
4937
1739
3489
1253
2514
919
1845
685
1376
10K
20K
Resistance (Ω)
12555
25099
8025
16057
5279
10569
3563
7139
2463
4937
1739
3489
1253
2514
919
1845
685
1376
Resistance (Ω)
20
12555
30
8025
40
5279
50
3563
60
2463
70
1739
80
1253
90
919
100
685
10K
20K
Resistance (Ω)
12555
25099
8025
16057
5279
10569
3563
7139