Laars MagnaTherm HTD Series Installation And Operation Instructions Manual page 127

Boilers and water heaters
Hide thumbs Also See for MagnaTherm HTD Series:
Table of Contents

Advertisement

Error
Diag.
Code
Code
Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
83
16
Interruption of speed signal
32
Quick shutdown due to excessive speed deviation
64
VSD speed is below minimum speed (phase dependent)
83
128
VSD speed exceeds maximum speed (phase dependent)
255
Failed forced travel test
Any #
Curve slope actuators
1
VSD: Curve too steep in terms of ramp speed
84
2
Fuel actuator: Curve too steep in terms of ramp rate
4
Air actuator: Curve too steep in terms of ramp rate
Any #
Referencing error on actuators
0
Referencing error of fuel actuator
85
1
Referencing error of air actuator
128
Referencing error due to parameter change
Any #
Error fuel actuator
HTD
Meaning for the LMV3
Corrective Action
No speed signal was detected.
1) Ensure that the motor is rotating. If it is not, check the wiring of the
VSD / PWM blower.
2) If using a VSD, turn the motor by hand to ensure that the LED on the
speed sensor lights up when it sees the speed wheel. If it does not,
decrease gap between speed wheel and speed sensor and check the
wiring of the speed sensor. If there are no issues, replace speed sensor.
The speed of the motor was more than 10% different than the anticipated
speed for more than 1 second.
1) Check the ramp times of the VSD and LMV3. Increase if necessary.
The ramp times in the LMV3 should be at least 20% longer than the ramp
times in the VSD.
2) Check the setting of parameter 661.
1) Standby (phase 12): Ensure parameter 669:01 (maximum speed) is set
to a higher value than parameter 669:00 (minimum speed).
2) Standby (phase 12): Ensure parameter 663 (near zone) is set to a
higher value than parameter 662 (neutral zone).
3) Check the absolute speed (parameter 935) to ensure the correct speed
is being detected by the LMV3.
4) Prepurge (phase 30): The detected speed was below the minimum
prepurge speed (parameter 667), or the setting of parameter 503:01 or
506:01 is below the setting of parameter 667.
5) Operation (phases 40-64): The detected speed was below the
minimum operation speed (parameter 669:00), or a VSD curve point was
set below the setting of parameter 669:00.
1) Standby (phase 12): Ensure parameter 226/266/326/366 is set to a
higher value than parameter 665 (time outside near zone).
2) Standby (phase 12): Ensure parameter 669:01 (maximum speed) is set
to a higher value than parameter 669:00 (minimum speed).
3) Standby (phase 12): Ensure parameter 663 (near zone) is set to a
higher value than parameter 662 (neutral zone).
4) Check the absolute speed (parameter 935) to ensure the correct speed
is being detected by the LMV3.
5) Ignition (phase 38): The detected speed was above the maximum
ignition speed (parameter 668), or the VSD speed setting of P0 is above
the setting of parameter 668.
6) Operation (phases 40-64): The detected speed was above the
maximum operation speed (parameter 669:01), or a VSD curve point was
set above the setting of parameter 669:01.
If the LMV3 remains at the same fire rate for an extended period of time,
a minimal load change is forced, and the corresponding feedback from
the PWM blower is checked. If this fault occurs, the PWM blower speed
change was insufficient in response to the load change.
The difference in position between two adjacent curve points is too large.
See diagnostic code for which actuator / VSD has positions that are too far
apart. For actuators, either increase the setting of parameter 544, or
decrease the distance between curve points. For VSD, either increase the
setting of parameter 544, decrease the setting of parameters 522 and
523, decrease the distance between curve points, or decrease parameter
647.
All SQM33... actuators must travel outside of their 0-90° operating range
before starting up the burner in order to "reference" their position. This
fault means that the referencing was unsuccessful.
1) Check the setting of parameter 601 (fuel 0) and 608 (fuel 1). Index 00
sets the fuel actuator reference direction and index 01 sets the air
actuator reference direction.
2) Check to make sure the actuators are not binding when trying to
reference (ensure that overstroking below 0° or above 90° is possible).
3) Check the setting of parameter 613 (fuel 0) and 614 (fuel 1) to ensure
the actuator type is set correctly.
4) Make sure that the actuator's are plugged into the correct terminal on
the LMV3.
An error occurred pertaining to the fuel actuator. See diagnostic codes
for more information.