System Installation
3.3.2.1

DC Power Cable

Power is introduced to the shelf via redundant DC PEMs. The recommended power cable is an
4 AWG gauge that meets the specifications for this shelf. There are four lugs for each PEM. Two
are straight and the other two are custom offset lugs. The end that connects to the external DC
power source should be equipped with an 8mm terminal.
Always check with your local building authorities for wire sizing requirements for your
environment.
The installation must comply with the 1993 National Electric Code (NEC) and other
applicable codes.
The DC power inputs must only be attached to approved Telephone Network Voltage (TNV)
or SELV (Safety Extra Low Voltage) branch circuits. Branch circuits must comply with all
requirements called for in these safety standards: IEC 60950, EN 60950, CAN/CSA-C22.2 No.
60950. Attaching inputs to non-TNV/SELV approved power sources will cause the system to
fail compliance with safety regulations.
The ground wire must be connected to a reliable earth ground connection to comply with
Class 1 Equipment requirements.
Multiple power sources are present.
Service only by qualified service personnel.
Mehrfache Energiequellen.
Handhabung nur durch geschultes Personal.
Des sources multiples de pouvoir sont présentes.
L'entretien de cet équipement doit être effectué par du personnel de service qualifié.
Wire
Earth Ground
Input power
Return
54
Signal
PE GND (Primary Earth Ground)
-48VDC nominal to -60VDC
-48VDC RETURN
AXP 1410 Installation and Use (6806800H70F)