Acs Engineering; Engineering; Commissioning - Siemens QMX3.P37 Technical Principles

Wall-mounted sensors and room operator units for knx/ets and knx/acs
Hide thumbs Also See for QMX3.P37:
Table of Contents

Advertisement

ACS790 version
Recommendation:
Keep the adhesive
address labels

Commissioning

prerequisites
Pushbuttons
LED status indication
Commissioning with
ACS
44 / 46
Siemens
Building Technologies
6

ACS engineering

6.1

Engineering

Tool ACS790 is used for engineering with devices from the Synco 700 range. This
tool is documented in Service- and Operating software ACS790 [6].
For ACS790, version 8.23 or higher must be installed.
During room operator unit mounting, the address labels can be peeled off the
devices and stuck to a floor plan or similar to show the KNX IDs and the physical
location in one place.
After mounting/installation, the devices are detected after updating the ACS790
device list. The devices can be easily identified in the device list based on the
collected KNX IDs, and the physical addresses can be assigned as planned. As a
result, commissioning requires only very little effort.
6.2
Commissioning
Depending on the environment, both type and number of adjustable parameters
will vary. Prior to commissioning, all devices must be mounted as per the mounting
instructions [2] and connected to bus cabling. If available, pushbuttons and
external temperature sensors must also be connected to the device. Bus cabling
must be tested.
Pushbutton actuation
Short (< 0.5 s)
Long (> 20 s)
LED indication
Orange
Red
All other indication types are irrelevant for KNX LTE-Mode.
Room sensor QMX3, KNX LTE–Mode controllers, and operator units are
connected to power. Update first the ACS790 device list, then open.
 Variant 1 (recommended)
1. Select a room operator unit from the device list via the KNX ID
(KNX-IDs must be collected during mounting).
2. Double-click this line to open the "Address assignment" dialog.
or
Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
ACS engineering
Meaning
Switch over to programming mode or acknowledge display of a
connection test.
No functions are executed when the programming button is
pressed longer (> 0.5 s to 2 s).
Reset to factory settings.
Meaning
Feedback on special mode.
Device is in programming mode.
CM2N1602en_05