Siemens QMX3.P37 Technical Principles page 28

Wall-mounted sensors and room operator units for knx/ets and knx/acs
Hide thumbs Also See for QMX3.P37:
Table of Contents

Advertisement

Obj. Object name
Room humidity sensor
25 Room relative humidity [%]
Provides the room humidity value from the integrated sensor.
Units with display: Must be placed in a group address to display operation/symbol on the display.
External room humidity sensor values, see object 70
External outside humidity sensor values, see object 69
Room humidity control
26 Switching point r.h. - stage 1
27 Switching point r.h. - stage 2
28 Switching point r.h. - stage 3
The configured default switching points apply as long as no value is received from the bus.
29 Control value r.h. cont. - manual setp.
In manual mode (obj. 30, 1=Manual), a setpoint is received via this object and outputted directly as modulating positioning
signal (object 36).
30 Control value r.h. cont. - manual mode
Changing over to the manual mode permits receipt of a manual setpoint (Obj. 29) for the modulating positioning signal
(Obj. 36). Otherwise, the configured positioning signals for the applicable stage are outputted.
31 Enable room r.h. controller
All controller outputs are switched off upon receipt of "Controller off".
The controller remains disabled until "Controller on" is received. The default value is controller on = 1.
32 Override room r.h. controller
For controller override, the stage defined in the parameter "Stage is overridden" is enabled. Objects 33, 34, 35 assume
only the value "1=On" for the corresponding object; the other two objects the value "0 = Off". The modulating positioning
signal (obj. 36) outputs the value configured for the applicable stage.
Override has the highest priority. The default state is "Normal".
33 Control value r.h. stage 1 - on/off
34 Control value r.h. stage 2 - on/off
35 Control value r.h. stage 3 - on/off
The stage belonging to positioning signal r.h. is switched on if room humidity overrides a
switching point r.h. The positioning signal r.h. is switched off again for room humidity <
switching r.h. - hysteresis.
36 Control value r.h. - cont
The positioning signal configured for the stage is outputted if room humidity overrides a
switching point r.h. The positioning signal once again outputs the value of the next smaller
stage, for room humidity < switching r.h. - Hysteresis.
28 / 46
Siemens
Building Technologies
Function
relative room humidity in %
relative humidity in %
relative humidity in %
relative humidity in %
Setpoint in 0 to 100%
Manual/Auto mode
On/Off
Ventilation (Boost) on/off
1 = On / 0 = Off
2 = On/0 = Off
3 = On/0 = Off
0 - 100%
Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
ETS engineering
Type / Length Flags
9.007
CRWU
2 bytes
9.007
CRWU
2 bytes
9.007
CRWU
2 bytes
9.007
CRWU
2 bytes
5.001
CRWU
1 byte
1.003
CRWU
1 bit
1.003
CRWU
1 bit
1.003
CRWU
1 bit
1.001
CRT
1 bit
1.001
CRT
1 bit
1.001
CRT
1 bit
On
Off
On
Off
On
Off
Swithing
Switching
point stufe
point 2
1
5.001
CRT
1 byte
[%]
Pos. signal stage 3
Pos. signal stage 2
Pos. signal stage 1
Pos. Sig. Stage 0
Switching
Switching
point
point
stage 1
stage 2
Devices
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Hysteresis
Pos.signal stage1
Pos. signal stage 2
Pos. Signal stage 3
[ppm CO2]
Switching
[% r.H.]
point 3
X
X
X
X
X
X
X
Hysteresis
Pos., signal
modulating
Switching
[ppm CO2]
point
[% r.H.]
stage 3
CM2N1602en_05
2018-09-14