Designation
Visible parameter name in ETS
5.5.5
Room air quality sensor
CO
concentr.: Send following change by
2
CO
concentr.: Sensor correction (ppm)
2
CO
concentr.: Send cyclically after
2
CO
concentr.: Altitude above sea level (m)
2
5.5.6
Room air quality control
To display this section, enable the option "Activate room air quality control" in Device
Default switching point stage 1 (ppm)
Default switching point stage 2 (ppm)
Default switching point stage 3 (ppm)
Hysteresis
If the CO
concentration exceeds a switching point CO
2
value CO
for the related stage is switched on. The control value CO
2
is again switched off, if the CO
point CO
– hysteresis.
2
Control value stage 0 (%)
Control value stage 1 (%) (>stage 0)
Control value stage 2 (%) (>stage 1)
Control value stage 3 (%) (>stage 2)
If the CO
concentration exceeds a switching point CO
2
value CO
for the related stage is switched on. The control value
2
issues again the value of the next lower stage when CO
concentration < switching point CO
Stage when overridden
Send cyclically after
5.5.7
Device display parameters
Backlight Level
Backlight idle time
Active unit set
Active audio feedback (buttons)
LED Brightness
Display: Idle page
(HVAC operation and display)
Time to return to idle page (s)
38 / 46
Siemens
Building Technologies
, the control
2
concentration returns to < switching
2
, the control
2
2
– hysteresis.
2
Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
ETS engineering
Values
Range
(Default)
5;10;20...500;750;1000
(10ppm)
-500...+500 (0 ppm)
1;2;3...30;45;60 (15 min)
0...5000 (0 m)
400...2000 (800)
400...2000 (1000)
400...2000 (1500)
50...500 (100)
2
0...100 (0)
0...100 (35)
0...100 (70)
0...100 (100)
0;1;2;3 (3)
Do not send cyclically
1;2;3...30;45;60 (15 min)
0; 10;...100 (60%)
3...20 (15 s)
°C; °F (°C)
yes; no (yes)
0...100 (100)
Temperature
Relative humidity
Air quality
3...120 (15 s)
Type
X
X
ppm
ppm
X
X
X
X
min
min.
X
X
X
X
X
X
X
X
ppm
ppm
X
X
X
X
X
X
ppm
X
X
X
X
X
X
X
X
X
X
X
X
ppm
%
X
X
X
X
X
X
%
X
X
X
X
X
X
X
X
X
X
X
X
%
%
X
X
X
X
X
X
X
X
X
X
X
X
min.
X
X
X
X
X
X
%
X
X
X
s
X
X
X
X
X
X
X
X
X
%
X
X
X
X
X
X
X
s
CM2N1602en_05
2018-09-14
X
X
X
X
X
X
X
X
X
X
X