Commissioning with
ACS and ETS
Siemens
Building Technologies
Variant 2
1. Set addressing mode for the room operator unit (briefly press button on
device LED is red).
2. In the ACS790 device list, use "Addressing mode..." to select the
currently active device Enter a physical address in the "Address
assignment" dialog Click "Write".
Enter a physical address and short description for the selected room operator
unit.
Close the "Address assignment" dialog by clicking "Write...".
Repeat these steps for all room operator units to be commissioned.
Then: Continue parameterization in ACS790.
The sensor can be operated in both communication modes at the same time.
To do this, commissioning with both ACS and ETS is required.
Only the sensor values (T, R.F., CO
Synco ACS.
To activate them set the zones accordingly in ACS.
ACS settings and ETS settings do not influence each other.
Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
ACS engineering
) of the QMX3... devices can be used with
2
45 / 46
CM2N1602en_05
2018-09-14