Installation and Operating Instructions | idOil-OIL
6.

Functional test

Always check the correct operation of the alarm after the installation and after making the
connections. You should also check the operation every time the separator is emptied or at
least once every six months.
6.1.

idOil-OIL sensor functional test with idOil control unit

Functional test:
1.
The sensor is in the water. The control unit should be in normal mode; indicator lights
are off (idOil-20) and there are no alarm notifications on the screen (idOil-30 and idOil-
D30), the relays are energised and the buzzer is silent.
2.
Lift the sensor in the air or the oil. The control unit's Oil chamber full indicator light
should light up or an alarm notification should appear on the screen within 10
seconds, after which the relay(s) should be de-energised, the buzzer should let out an
alarm sound and the local screen's backlight should start blinking after the set delay.
3.
Lower the sensor back into the water. The indicator light should turn off or the alarm
notification should disappear within 10 seconds and the relay(s) and the buzzer
should revert to their normal state after the set delay.
Clean the sensor of any contaminants that it might have accumulated during the functional
test before placing it back in the separator.
If the sensor does not function as described, check the device settings from the control
unit's installation and operating instructions or contact the representative of the
manufacturer.
6.2.

idOil-OIL sensor functional test with SET control unit

Functional test:
1.
The sensor is in the water. The control unit should be in normal mode; indicator lights
are off, the relays are energised and the buzzer is silent.
2.
Lift the sensor in the air or the oil. The control unit's Oil chamber full indicator light
should light up within 10 seconds, after which the relay(s) should be de-energised and
the buzzer should let out an alarm sound after the set delay.
3.
Lower the sensor back into the water. The indicator light should turn off within 10
seconds and the relay(s) and the buzzer should revert to their normal state after a
delay.
Clean the sensor of any contaminants that it might have accumulated during the functional
test before placing it back in the separator.
If the sensor does not function as described, check the device settings from the control
unit's installation and operating instructions or contact the representative of the
manufacturer.