4 Planning

4.1 Compatibility

4.2 Fields of application

4.3 Mounting site

Building Technologies
Fire Safety
Please always take the country-specific provisions and the alarm organization for
project planning into account. In addition, the connection factors stated in the
specifications must also be taken into account.
Compatible with control panels that support the FDnet-Ex/C-NET-Ex detector line.
The table below shows the compatibility of the manual call point with various
control panels:
Detector line
FC20xx
FDnet-Ex
C-NET-Ex
X = compatible
X
= compatible with line card (FDnet/C-NET)
1
– = not compatible
You will find detailed information in the 'List of compatibility'.
See also
2 Applicable documents [➙ 9]
The manual call points are intended for use in places where a fire can be detected
by people who can manually trigger an alarm.
The manual call points must be installed in easily accessible places at a height of
0.9...1.6 m on an even surface.
Observe the country-specific regulations for the exact mounting height!
Control panel
FC72x
X
X
Planning
Compatibility
SIGMASYS
AlgoRex
X
X 1
1
A6V10349616_i_en_--
2019-01-18
4
25 | 42