ABB ACS580MV Hardware Manual page 47

200 kw to 6300 kw, 6 kv to 11 kv
Hide thumbs Also See for ACS580MV:
Table of Contents

Advertisement

Customer Interface Terminal Block
X1
Customer Interface Terminal Block
1
MCB close cmd
3
5
7
MCB open cmd
9
11
13
MCB trip/unlock cmd 1
15
17
19
MCB closed status
21
23
MCB open status
25
27
MCB ready status
29
31
Emergency off 1
33
35
Emergency off 2
37
41
Remote MCB close cmd
43
45
Remote MCB open cmd
47
53
Alarm
55
57
Emergency off reset
59
61
62
63
24Vdc
64
65
66
67
Customer interface terminal block
floating contacts to customer
making capability: 40 A
thermal current: Ith = 6 A @40°C
breaking capability:
AC-15 50 Hz Ie(240 V)=4 A, Ie(500 V)=2 A
DC-13 Ie(24 V)=2.5 A, Ie(110 V)=0.7 A, Ie(240 V)=0.4 A
minimum load: 17 V, 5 mA
isolation rated voltage 690 V AC
Connect contact from customer
internal supply 24 Vdc, 5mA
Connect contact from customer
internal supply 24 Vdc, 5 mA, max resistance 140 Ω
Connect contact from customer
internal supply 24 Vdc, 5mA
Connect contacts from customer
Max resistance 60 Ω .
Internal supply, 24 Vdc, 25 mA
Connect contacts from customer
internal supply 24Vdc, 5 mA
Switchable
RO, NC/NO can be selective, 250 V AC/24 V DC,2A
to be check
24Vdc for digit input
Control system and interfaces 47