Process Display - ABB VAC D500 Commissioning Instructions

Electro-pneumatic positioner
Table of Contents

Advertisement

7.2.1

Process display

-
1
6
Position
POS
5
3
Fig. 21: Process display (example)
1 Measuring point identifier |
2 Display showing current process values |
3 Symbol indicating button function |
4 Symbol indicating "Parameterization protected"
5 Diagnostic message | 6 Operating mode symbol
The process display appears on the LCD display when the
device is switched on. It shows information about the device
and current process values.
The way in which the current process values (2) are shown
can be adjusted on the configuration level.
Description of symbols
Symbol
Description
Call up information level.
When Autoscroll mode is enabled, a  symbol
appears here and the operator pages are
automatically displayed one after the other.
Call up configuration level.
The device is protected against changes to the
parameter settings.
D500
22 CI/EDP300-EN Rev. A |
50.0
%
4
3
M10240
Description of operating modes
Symbol
2
Operating mode
Adaptive control active
When the PositionMaster EDP300 positioner is
operated in "Adaptive Mode", the control
parameters are automatically optimized to the
operating conditions in small increments. This is
especially helpful if valves and fittings could not be
operated with reference conditions while the Auto
Adjust function was in progress.
The self-optimization process in "Adaptive Mode" is
affected by several factors that can result in
incorrect adjustments in the long term. It is
recommended that this operating mode is only
activated over several hours and that the "Fixed
control" operating mode is selected following this.
Fixed control
In contrast to the "Adaptive control" operating
mode, the control parameters are not automatically
adjusted.
Manual setpoint, adaptive control
The valve is adjusted manually within the stroke
range using the
or
direction buttons.
1. Press and hold the relevant operating button for
the desired direction.
2. Additionally, press
if the device is to be
switched to high-speed mode.
CAUTION – Risk of crushing
Configured stroke limit positions
and stroke times are not effective in
manual mode. When the actuator
moves, there is a risk of crushing.
You must make sure that no-one is
present within the actuator's
working range.

Advertisement

Table of Contents
loading

Table of Contents