4.2

Cable entry

For the cable entry in the housing, there are two tap holes 1/2
- 14 NPT or M20 x 1.5 on the left-hand side of the housing.
One of these holes has a cable gland and the other has a pipe
plug.
1
2
Fig. 17
1 Pipe plug | 2 Cable gland
4.3

Installing the option modules

IMPORTANT (NOTE)
If you are using the "emergency shutdown
module", there must be a supply voltage of 24 V
DC at terminals +41 / -42. Otherwise, the
positioner will not be able to function
pneumatically (device in pneumatic safety
position).
IMPORTANT (NOTE)
A functional check of the "emergency shutdown
module" (option) must be performed at least every
2 years. For this purpose, the positioner must
move the valve into the safety position with the 24
V DC signal (terminals +85 / -86) interrupted.
D500
16 CI/EDP300-EN Rev. A |
4.3.1
Fig. 18: Printed circuit board
1 I/P converter pneumatics | 2 Position sensor |
M10131
3 Pressure option
4.4

Setting the option modules

4.4.1
1. Loosen the screws for the housing cover and remove it.
2. Rotate the position indicator on the feedback shaft to the
desired position.
3. Attach the housing cover and screw it onto the housing.
Tighten the screws so that they are hand-tight.
4. Attach the symbol label to mark the minimum and
maximum valve positions on the housing cover.

Installing the pressure option

1
2

Setting the mechanical position indicator

IMPORTANT (NOTE)
The labels are located on the inside of the
housing cover.
3
M10144