Profisafe Configuration; Import Edd With Simatic Pdm; Configure Cpu With Hw Config - Siemens SITRANS P Series Supplement To Operating Instructions

Pressure transmitter
Hide thumbs Also See for SITRANS P Series:
Table of Contents

Advertisement

1.5

PROFIsafe Configuration

For safety reasons, the PROFIsafe device is supplied with default settings.
Requirement
Before you commission the PROFIsafe device, configure it in Step7 – for example.
Process
Import EDD with SIMATIC PDM (Page 1-3)
Configure CPU with HW Config (Page 1-3)
Configure device with HW Config (Page 1-4)
Configure CFC (Page 1-4)
1.5.1

Import EDD with SIMATIC PDM

To import the EDD, click on "SIMATIC PDM" > "Manage Device Catalog".
1.5.2

Configure CPU with HW Config

The relevant settings for fail-safe of the CPU are located in the CPU-specific documentation.
Procedure
If your CPU is a SIMATIC CPU, proceed as follows:
1. Double click on the CPU.
2. You are now in the "Properties" dialog box on the "Protection" tab. Activate the following
SITRANS P, DS III PROFIsafe series
Supplement to Operating Instructions, 03/2006, A5E00732533-01
checkboxes:
– Protection level "1"
– "Removable with password"
– "CPU contains safety program"
PROFIsafe
1.5 PROFIsafe Configuration